| Plan Review Notes For Permit 10090780 |
| Permit Number |
10090780 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-18 14:34:08 | 3111-45TH STREET | | | PERMIT NUMBER 10090780 | | | "TENANT IMPROVEMENT" | | | | | | | | | 1. PLAN SHEETS CONFLICT IN SOME INSTANCES. ON ONE SHEET | | | IT INDICATES THAT FIRE SPRINKLERS ARE PRESENT AND ON | | | ANOTHER IT INDICATES THAT NO FIRE SPRINKLER EXIST. | | | PLEASE CORRELATE INFORMATION. | | | | | | 2. ANOTHER EXIT SIGN IS NEEDED NEAR ROW OF D20 LIGHT | | | FIXTURES TO DIRECT PERSONS THROUGH DOORWAY. | | | | | | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 4. PLANS DO NOT ILLUSTRATE PORTABLE FIRE EXTINGUISHER | | | LOCATIONS. | | | | | | 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | | WALLS AND CEILINGS | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | |
|