Date Text
2010-10-18 14:34:083111-45TH STREET
 PERMIT NUMBER 10090780
 "TENANT IMPROVEMENT"
  
  
 1. PLAN SHEETS CONFLICT IN SOME INSTANCES. ON ONE SHEET
 IT INDICATES THAT FIRE SPRINKLERS ARE PRESENT AND ON
 ANOTHER IT INDICATES THAT NO FIRE SPRINKLER EXIST.
 PLEASE CORRELATE INFORMATION.
  
 2. ANOTHER EXIT SIGN IS NEEDED NEAR ROW OF D20 LIGHT
 FIXTURES TO DIRECT PERSONS THROUGH DOORWAY.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PLANS DO NOT ILLUSTRATE PORTABLE FIRE EXTINGUISHER
 LOCATIONS.
  
 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  