| Plan Review Notes For Permit 10090778 |
| Permit Number |
10090778 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-11-22 14:19:04 | 4295 45TH STREET | | | SAM'S CLUB (CLASS A - MERCANTILE) | | | PERMIT #10090778 | | | MASTER #09070775 | | | | | | | | | SHEET EFP2: REVISE BOTH MATRICIES (SEQUENCE OF | | | OPERATIONS & POINT TYPE) TO HAVE THE DUCT SMOKE | | | DETECTORS ACTIVATE THE GENERAL FIRE ALARM SYSTEM AND | | | TRANSMIT AN ALARM SIGNAL TO THE MONITORING COMPANY. |
|