| Date |
Text |
| 2010-10-01 13:54:03 | 4295-45TH STREET |
| | PERMIT NUMBER 10090778 |
| | " PROVIDE A NEW FIRE ALARM SYSTEM WITH FULL |
| | NOTIFICATION THROUGHOUT BUILDING" |
| | |
| | 1. THE ENTIRE FIRE ALARM SYSTEM SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NFPA 72, 2002 EDITION. |
| | |
| | 2. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN |
| | OPERATIONAL UNTIL SUCH TIME AS THE NEW FIRE ALARM |
| | SYSTEM IS INSTALLED, INSPECTED, TESTED, AND APPROVED BY |
| | CITY OFFICIALS. |
| | |
| | 3. ANY TIME THE REQUIRED FIRE ALARM SYSTEM IS OUT OF |
| | SERVICE FOR MORE THAN 4 HOURS IN A TWENTY FOUR HOUR |
| | PERIOD, A FIRE WATCH IS REQUIRED. ALL FIRE WATCH |
| | ACTIVITIES SHALL BE IN WRITING TO THE BATTALION CHIEF |
| | OF FIRE PREVENTION OR HIS DESIGNEE. FIRE WATCH |
| | PERSONNEL SHALL HAVE NO OTHER DUTIES EXCEPT TO REPORT |
| | EMERGENCIES. THEY SHALL BE RADIO OR CELLULAR TELEPHONE |
| | EQUIPPED AND A LOG MAINTAINED. |
| | |
| | 4. ACCORDING TO LOCAL POLICY, DUCT DETECTORS WHEN |
| | ACTIVATED SHALL ACTIVATE THE FIRE ALARM SYSTEM NOT A |
| | SUPERVISORY SIGNAL. |
| | |
| | 5. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT |
| | LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. |
| | |
| | 6. PLEASE INDICATE CIRCUITS FOR SIGNALING AND |
| | INITIATING APPLIANCES ON THE FLOOR PLAN. |
| | |
| | 7. IS THERE ANY FIRE ALARM DEVICES PLANNED FOR THE |
| | REMODELED TIRE AND BATTERY STORAGE AREA AND THE |
| | REFRIGERATION MECHANICAL CENTER OR THE EXISTING |
| | DEHUMIDIFIER AREAS. |
| | |
| | 8. NOTE # 12 AND 13 ARE CROPPED OFF ON SHEET EFP2. |
| | |
| | 9. THE FIRE ALARM SYSTEM WHEN ACTIVATED SHALL PROVIDE |
| | FOR ADEQUATE AUDIBILITY THROUGHOUT THE STORE. ENOUGH |
| | VISUAL DEVICES SHALL BE PROVIDED THROUGHOUT THE STORE. |
| | |
| | 10. SIGNALS TO BE PROVIDED TO THE CENTRAL STATION |
| | INCLUDE WATERFLOW, GENERAL ALARM, SUPERVISORY, AND |
| | TROUBLE SIGNALS. |
| | |
| | 11. PLEASE ADD NOTES TO THE PLANS TO REFLECT THE ABOVE |
| | INFORMATION. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |