| Notes |
| Date |
Text |
| 2010-10-22 10:32:17 | RESIDENTIAL (R3) ADDITION/RENOVATION MECHANICAL REVIEW | | | CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PROVIDE COOLING AND HEATING LOAD CALCULATIONS AS | | | REQUIRED BY SEC. N1107 OF 2007 FLORIDA RESIDENTIAL | | | CODE. | | | | | | ***NOTE: NO RETURN AIR ALLOWED FROM CLOSET OR BATHROOM. | | | RETURN AIR TO BE DUCTED AS SHOWN ON SECOND FLOOR PLAN | | | ON SHEET M1 AND DETAIL ON SHEET M2. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|