| Date |
Text |
| 2010-10-15 15:23:58 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 OF THE |
| | 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED |
| | ON EXPOSURE "C" NOT EXPOSURE "B". REVISE STRUCTURAL |
| | DRAWINGS AS REQUIRED. ENGINEER NEEDS TO REVISE THE |
| | DESIGN CRITERIA AND THE COMPONENTS AND CLADDING DESIGN |
| | PRESSURES ON THE STRUCTURAL DRAWINGS. |
| | |
| | 2- ENGINEER NEEDS TO INCREASE 20% ON THE ROOF SHEATHING |
| | AND ROOF-TO-WALL UPLIFT LOADS AS REQUIRED BY 2009 |
| | REVISIONS SEC. R301.2.1.4.3(2). |
| | |
| | 3- BRING PLANS TO THE HISTORIC DEPARTMENT FOR HISTORIC |
| | APPROVAL STAMP BEFORE SUBMITTING THEM TO THIS OFFICE. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | (A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. PRODUCT |
| | APPROVAL SUBMITTED IS FOR FIXED WINDOWS. THERE ARE NOT |
| | FIXED WINDOWS SHOWN ON PLANS. AND, NOA 08-1112.10 |
| | SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. |
| | |
| | (B) SLIDING WINDOWS AS SHOWN ON PLANS. |
| | |
| | (C) FLAT ROOF SYSTEM TO BE USED: (1 )NOA SPECIFIED ON |
| | ROOF FRAMING PLAN IS NOT THE SAME NOA THAT WAS |
| | SUBMITTED. AND, IT CAN'T BE USED BECAUSE IT WAS |
| | SUPERSEDED BY MIAMI-DADE. REVISE PLANS AND PRODUCT |
| | APPROVAL TO MATCH. SEE MIAMI-DADE WEBSITE FOR CURRENT |
| | PRODUCT APPROVALS. |
| | (2) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING |
| | TO BE USED. |
| | (3) PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL |
| | LIMITATION #7. IF NOA SUBMITTED REQUIRES SIGNED AND |
| | SEALED RAS 117 CALCULATIONS, THEN PROVIDE SIGNED AND |
| | SEALED CALCULATIONS. |
| | (4) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS |
| | TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C". |
| | (5) FLAT ROOF NOA 07-0730.03 SUBMITTED WAS SUPERSEDED |
| | BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. SEE |
| | MIAMI-DADE WEBSITE. AND PROVIDE RAS 117 CALCULATIONS. |
| | SEE ITEM (C)(3) ABOVE. |
| | |
| | (D) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | (E) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS. |
| | |
| | (F) EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 6- PROVIDE WINDOW CUT SHEETS SHOWING THAT 36"X56" |
| | SINGLE HUNG WINDOW MEET THE MIN. CLEAR OPENING REQUIRED |
| | OPENING AREA TO BE 5.7 S.FS AS REQUIRED BY SEC. |
| | R310.1.1 AND R310.1.2 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 8- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED |
| | BY 2009 REVISIONS SEC. R313.4 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 9- REVISE OVERFLOW SCUPPERS SHOWN ON SHEET A2.3 TO |
| | COMPLY WITH SEC. R903.4.1 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. REVISE LOCATION OF MAIN SCUPPERS AND OVERFLOW |
| | SCUPPER IN RELATION TO THE ROOF FINISH. SEE SEC. R903.4 |
| | AND R903.4.1. |
| | |
| | 10- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806. |
| | |
| | 11- CLARIFY HOW INSTALLING R-30 BUTT INSULATION ON ROOF |
| | DECK. AS SHOWN ON WALL SECTIONS AND DETAILS ON SHEET |
| | A3.2 AND A3.3. REVISE AS REQUIRED. |
| | |
| | 12- REVISE STUCCO THICKNESS ON WOOD FRAMED WALLS NEED |
| | 7/8" MIN. THICKNESS. SEE TABLE R702.1(1). REVISE ALL |
| | WALL SECTIONS AND WALL LEGEND SPECIFICATIONS. |
| | |
| | 13- PROPOSED 2ND FLOOR PLAN ON SHEET A2.1 SHOWS 2'X3' |
| | ATTIC ACCESS. THIS IS A FLAT ROOF. CLARIFY/REVISE AS |
| | REQUIRED. |
| | |
| | 14- PARTIAL SECOND FLOOR PLAN ON SHEET S2 SHOWS BEAMS |
| | RUNNING THRU CHASE OF EXISTING CHIMNEY. PROVIDE DETAILS |
| | AND SPECIFICATIONS SHOWING COMPLIANCE WITH SEC |
| | R1001.11. AND, THE FIREBLOCKING AND DRAFSTOPPPING |
| | REQUIREMENTS. |
| | |
| | 15- REVISE ALL WALL SECTIONS AND WALL SCHEDULE |
| | SPECIFICATIONS TO SPECIFY 2 LAYERS OF WATER RESISTANT |
| | BARRIERS AS REQUIRED BY SEC. R703.6.3. |
| | |
| | 16- ENERGY CALCULATIONS: |
| | A) ITEM #8 IS MISSING THE COMMON FLOOR. THIS IS A 2 |
| | STORY ADDITION. |
| | B) CLARIFY HOW OBTAINING R6 INSULATION ON THE MASONRY |
| | WALL. AND, COORDINATE WITH INFORMATION SHOWN ON PLANS. |
| | C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | D) COMPLETE ALL THE INFORMATION ON TOP OF THE FORM. |
| | E) COORDINATE R VALUE SHOWN ON ITEM #9(2) WITH |
| | INFORMATION SHOWN ON PLANS. |
| | F) REVISE ITEM #10. THERE IS NOT ATTIC ON THIS HOUSE. |
| | SEE PLANS. |
| | G) COMPLETE ALL THE INFORMATION ON TABLES 11B-1 AND |
| | 11B-2 ON SHEET 2. |
| | |
| | 17- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |