Date Text
2010-10-06 10:14:35PLANS DENIED
 1) PROVIDE DUCT SIZE ON THE PLANS.
 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 3) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS.
 4) REFER TO SECTION 601.4 BALANCED RETURN AIR 2007 FMC.
 5) SHOW THE LOCATION OF THE RETURN AIR ON THE
 MECHANICAL PLANS
 6) PLEASE SUBMIT A COMPLETE SET OF MECHANICAL PLANS FOR
 THE PERMIT.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  