| Plan Review Notes For Permit 10090637 |
| Permit Number |
10090637 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-04 14:23:40 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF THE WIND LOAD CALCULATIONS ( | | | REPORT HC-6) THAT ARE SIGNED AND SEALED BY THE ENGINEER | | | AS REQUIRED BY FS 471 AND FAC 61G15-23.002. | | | | | | 2) SPECIFY THE REQUIRED EMBED DEPTH OF THE SIMPSON | | | TITEN HD ANCHORS SPECIFIED ITEM V (2) OF THE WIND LOAD | | | CALCULATIONS. | | | | | | 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS (DCA | | | RULE9B-72) FOR THE 1/4" SIMPSON TITEN HD WITH THE | | | WITHDRAWL LOADS IN CONCRETE TILE SPECIFIED IN ITEM V | | | (2) OF THE WIND LOAD CALCULATIONS. | | | | | | 4) PROVIDE 2 COPIES OF PRODUCT APPROVALS FOR ROOF TILES | | | THAT HAVE BEEN TESTED WITH THIS APPLICATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|