| Date |
Text |
| 2010-10-07 15:31:49 | RESIDENTIAL (R3) REPAIRS/RENOVATION/ALTERATION BUILDING |
| | REVIEW CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- PROVIDE THE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE: PLEASE MAKE SURE CORRECT UPDATED FORM IS USED |
| | AND FILL ALL THE INFORMATION ON THE FORM. |
| | |
| | 3- PROVIDE PRODUCT APPROVALS AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | |
| | A) WINDOW MULLIONS. AND CLEARLY MARK ON MULLION |
| | DRAWINGS SPECIFIC MULLION SIZE AND FASTENERS TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) ARCHED WINDOWS AS SHOWN ON PLANS. NOA 08-0917.08 |
| | SUBMITTED IS FOR RECTANGULAR WINDOWS ONLY. AND PROVIDE |
| | 2 COPIES. |
| | |
| | C) SINGLE HUNG WINDOWS. ONLY ONE NOA WAS SUBMITTED. |
| | NEED TWO COPIES. |
| | |
| | D) FLAT ROOF ASSEMBLY: AND (1) CLEARLY MARK WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. (2) PROVIDE |
| | RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER |
| | AND CORNER AREAS. (3) RAS 117 CALCULATIONS TO BE SIGNED |
| | AND SEALED IF GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | REQUIRES THEM TO BE SIGNED AND SEALED. ***NOTE: |
| | ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE USED IN |
| | THIS BUILDING. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR |
| | TO SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 5- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | CHECK IF IMPACT FEES ARE DUE WHEN CONVERTING THE PORCH |
| | TO LIVING SPACE. BRING BACK STAMPED PLANS AND COPY OF |
| | PAID RECEIPT IF FEES ARE DUE. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |