| Plan Review Notes For Permit 10090578 |
| Permit Number |
10090578 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-18 11:53:34 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. | | | | | | 2. REVISE PLAN TO SPECIFY LETTER SIZES, FBC1609. | | | ENGINEER HAS SPECIFIED MINIMUM THREE 1 1/2" TAPCONS PER | | | LETTER, WITH NO LETTER SIZE. THIS PROPOSED INSTALLATION | | | IS FOR LETTERS WHICH APPEAR TO BE APPROXIMATELY 3'6" X | | | 4' EACH, LOCATED ON A HIGH RISE. WHO DETERMINES WHEN | | | MORE FASTENERS ARE REQUIRED? ARE THE THREE TAPCONS | | | ADEQUATE REGARDLESS OF LETTER SIZE? "MASTER" | | | ENGINEERING SHOULD INCLUDE A LIMITATION SUCH AS MAXIMUM | | | LETTER SIZE OR MAX DISTANCE BETWEEN FASTENERS. | | | | | | CALCUATIONS TO SHOW THAT FASTENING SPECIFIED IS | | | ADEQUATE MAY BE REQUIRED. | | | | | | |
|