| Date |
Text |
| 2010-10-22 11:10:28 | ****CORRECTIONS**** |
| | PERMIT APPLICATIONS 10090450, 10090451, 10090452, |
| | 10090453, 10090454, 10090455, 10090456, 10090458 |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. AN ENGINEERING EVALUATION AND SPECIFICATION FOR |
| | REPAIR REQUIRED, FS471. SEE ALSO CITY OF WEST PALM |
| | BEACH AMENDMENTS, FBC105.3. THE SCOPE OF STRUCTURAL |
| | REPAIRS PROPOSED DOES NOT FALL UNDER ANY EXCEPTION TO |
| | ENGINEERING. |
| | |
| | 2. THE LETTER PROVIDED REQUESTS THAT A PERMIT BE ISSUED |
| | FOR "EMERGENY REPAIRS IN THE FACE OF THE HURRICANES NOW |
| | PRESENT." PLEASE BE ADVISED THAT A SHORING PERMIT CAN |
| | BE ISSUED UPON REQUEST IF AN EMERGENCY CONDITION |
| | EXISTS. HOWEVER, STRUCTURAL REPAIRS WOULD REQUIRE |
| | PLANS. |
| | |
| | 3. PROVIDE A SITE PLAN WHICH SHOWS LOCATION OF PROPOSED |
| | REPAIRS. THE SITE PLAN FOR EACH PERMIT SHOULD SHOW THE |
| | BUILDING IN RELATION TO THE SITE AS WELL AS SPECIFIC |
| | LOCATION OF REPAIRS. APPLICATIONS WERE SUBMITTED WITH A |
| | SPECIFIC UNIT NUMBER AS ADDRESS. ARE REPAIRS FOR THIS |
| | UNIT ONLY OR TO THE COMMON AREA (EXTERIOR BUILDING |
| | STRUCTURE)? IF REPAIRS ARE TO THE ENTIRE BUILDING, |
| | PLEASE REVISE PERMIT APPLICATION. THE LETTER PROVIDED |
| | REFERS TO 13 BUILDINGS AND A CLUBHOUSE AND REPAIRS |
| | REQUIRED TO "THE BUILDINGS" BUT THE PERMIT APPLICATIONS |
| | APPEAR TO BE FOR BUILDING A. |
| | |
| | 4. THE LETTER PROVIDED REQUESTED PERMIT NUMBERS FOR |
| | BALCONY REPAIR WORK DONE IN THE PAST. ONE EXAMPLE |
| | PERMIT NUMBER IS 08120380. I DID NOT VERIFY WHETHER OR |
| | NOT THIS IS THE ONLY PERMIT FOR BALCONY REPAIRS. AS |
| | THIS IS A LARGE COMMERCIAL PROPERTY WITH NUMEROUS |
| | PERMITS, I AM UNABLE TO ACCOMODATE YOUR REQUEST. YOU |
| | CAN OBTAIN THIS INFORMATION AT OUR WEBSITE, HTTP://ONES |
| | TOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STATUS.ASPX. |
| | WHEN SEARCHING BY ADDRESS, ENTER ONLY "STREET NUMBER" |
| | (2800) AND "STREET NAME" (GEORGIA) AND LEAVE OTHER |
| | FIELDS BLANK. ALTERNATELY YOU CAN SUBMIT A PUBLIC |
| | RECORDS REQUEST. |
| | |
| | 5. PLEASE RESOLVE OTHER EXPIRED PERMITS FOR THIS |
| | ADDRESS AT THIS TIME. |
| | |
| | 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | EXTERIOR DOORS, FAC9B72, FBC1609. |
| | |
| | 7. PROVIDE A PLAN WHICH SHOWS PROPOSED DOOR REPLACEMENT |
| | LOCATION. |
| | |
| | 8. PROPOSED DESIGN PRESSURE REQUIREMENTS FOR EXTERIOR |
| | DOORS REQUIRED, FBC1603.1.4. |
| | |
| | 9. AFTER SCOPE OF WORK HAS BEEN DETERMINED, PROVIDE A |
| | COPY OF THE CONTRACT FOR THIS JOB. |
| | |
| | 10. ADVISORY ONLY, NOTICE OF COMMENCEMENT WILL BE |
| | REQUIRED PRIOR TO FIRST INSPECTION, FS713. |
| | |
| | |