| Plan Review Notes For Permit 10090442 |
| Permit Number |
10090442 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-05 15:51:14 | FAILED | | | | | | 1) THE SCALE FOR EACH DRAWING ON SHEETS A-1 AND A-1A IS | | | INCORRECT. | | | | | | 2) THE BUILDING HEIGHT ON THE COVER SHEET SHALL REFLECT | | | THE HEIGHT TO THE ROOF OF 102 FEET AS SHOWN ON SHEET | | | A1-A. | | | | | | 3) THE SITE WALK MAPPING PHOTOS SHOW EXISTING DISH | | | ANTENNAS AND OTHER INFRASTRUCTURE ON THE ELEVATOR | | | PENTHOUSE. HOW WILL THE EXISTING ANTENNAS AND | | | INFRASTRUCTURE BE PROTECTED DURING AND AFTER THE | | | INSTALLATION OF THE SCREEN WALL? WHAT MEASURES ARE | | | TAKEN TO ENSURE THAT THEY WILL CONTINUE TO FUNCTION | | | PROPERLY AFTER INSTALLATION? PERMITS MAY BE REQUIRED BY | | | THE CONSTRUCTION SERVICES DEPARTMENT IN THE EVENT ANY | | | EXISTING ITEMS ARE TO BE RELOCATED. | | | | | | 4) THE DRAWINGS DO NOT SPECIFY IF THE SCREENING PANELS | | | WILL BE MOUNTED TO ALL FOUR (4) SIDES OF THE SCREEN | | | WALL FRAME. PLEASE VERIFY THAT THE SCREENING PANELS | | | WILL BE MOUNTED TO ALL FOUR (4) SIDES. THE BUILDING | | | PERMIT PLANS SHALL CLEARLY SHOW THIS CONDITION. | | | | | | 5) THE CITY HAS NOT RECEIVED THE CITYSCAPE APPROVAL OF | | | THE WIRELESS INSTALLATION. | | | | | | 6) THE WIRELESS COMMUNICATION FACILITY APPLICATION HAS | | | NOT YET BEEN APPROVED BY THE ZONING DIVISION. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
|