Notes
Date Text
2010-09-28 12:56:40450 AUSTRALIAN AVENUE
 PERMIT NUMBER 10090442
 "ATTACH BROAD BAND ANTENNAS TO EXISTING BUILDING AND
 PLACE EQUIPMENT ON ROOF"
  
  
 1. ON SHEET A-1, W 4TH STREET APPEARS. WRONG STREET
 NAME AND WRONG LOCATION.
  
 2. ON SHEET A-1 CONDUIT APPEARS TO ENTER THE STAIRWELL
 ALONG WITH EQUIPMENT. PLEASE BE ADVISED THAT THE
 FLORIDA FIRE PREVENTION CODE (FFPC) SECTION 7.1.3.2.1
 (6) IDENTIFIES EQUIPMENT THAT CAN BE LOCATED IN AN EXIT
 ENCLOSURE.
  
 3. ON SHEET E-2 MORE EQUIPMENT APPEARS TO BE CONTAINED
 IN THE EXIT ENCLOSURE. PLEASE SEE ABOVE CODE SECTIONS
 FOR ALLOWABLE EQUIPMENT THAT CAN BE CONTAINED IN AN
 EXIT ENCLOSURE.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION