| Plan Review Notes For Permit 10090385 |
| Permit Number |
10090385 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-28 11:12:38 | 3319 SOUTH DIXIE HIGHWAY | | | PERMIT NUMBER 10090385 | | | "REMODEL EXISTING BUILDING" | | | | | | | | | 1. THE PERMIT APPLICATION INDICATES AN ADDRESS OF 3319 | | | SOUTH DIXIE HIGHWAY, BUT THE PLANS INDICATES AN ADDRESS | | | OF 3323 SOUTH DIXIE HIGHWAY. PLEASE CORRELATE | | | INFORMATION. | | | | | | 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 4. THE ROLL-UP SECURITY SHUTTERS ARE TO REMAIN IN THE | | | OPEN WHEN THE BUILDING IS OCCUPIED. | | | | | | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 6. A KNOX-BOX IS REQUIRED SINCE A FIRE ALARM SYSTEM IS | | | PLANNED. PLEASE CONTACT WWW.KNOX-BOX.COM TO ORDER A KEY | | | BOX. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | | INSTALLATION OF THE FIRE ALARM SYSTEM. THE FIRE ALARM | | | SYSTEM SHALL BE CLASS A OR FULLY ADDRESSABLE. | | | | | | 8. DUCT SMOKE DETECTORS UPON ACTIVATION SHALL INITIATE | | | A GENERAL ALARM. NOTE X ON PAGE F-1 IS INCORRECT. | | | | | | 9. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | | ALL WALLS AND CEILINGS. | | | | | | 10. PLEASE INDICATE LOCATIONS AND TYPES OF PORTABLE | | | FIRE EXTINGUISHERS CONTAINED WITHIN THE LOCATION. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|