2010-09-27 11:02:58BUILDING PLAN REVIEW
 PERMIT: 10090385
 ADD: 3319 S DIXIE HWY
 CONT: ABC LIQUORS, INC.
 TEL: (407)851-0000
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE COVER SHEET LIST AN INDEX OF PLANS, BUT NO PLANS
 ARE INDICATED AS A ROOF PLAN, NOTE A NEW PARAPET IS
 BEING ADDED PLEASE INDICATE COMPLIANCE WITH SECTION
 FBC-B 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO
 DRAIN OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF
 DRAINAGE SYSTEMS SHALL COMPLY WITH THE FLORIDA BUILDING
 CODE, PLUMBING CHAPTER 11. PLANS CURRENTLY INDICATE A
 GUTTER HEAD DETAIL 3 SHEET A-3 ALL DETAILS ON THIS
 SHEET ARE LABELED AS A-2, MISLABELED. PLANS DO NOT
 INDICATE IF THIS WILL BE THE SCUPPER OR OVERFLOW
 SCUPPERS, NOR IS THERE INFORMATION AS TO SLOPE OF ROOF
 FINSIH?
  
 2) PLEASE REVIEW ENERGY CALCULATIONS AND THE INSULATION
 VALUES FOR THE EXTERIOR WALLS. THE ENERGY CALCULATIONS
 INDICATE 3/4 " ISO INSULATION, NOTE THIS INSULATION IS
 TO CONTINUE TO THE UNDER SIDE OF THE ROOF. DETAIL # 5
 OF SHEET A-4 PLEASE REVIEW SECTION FBC-B 13-406.AB.3.2
 WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER
 CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER
 BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH
 AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED
 FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND
 ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS
 ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT
 CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER
 THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING.
  
 3A) SHEET M-1 INDICATES THE ROOF TOP EQUIPMENT CU# 1 &
 CU#2 ARE TO BE MOUNTED ON ROOF TOP STANDS. RULE
 9B-72(31)( G) WILL REQUIRE PRODUCT APPROVALS FOR
 PRE-ENGINEERED A/C STANDS.
  
 3B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3C) SHEET M-1 EQUIPMENT SCHEDULE REFERS TO STRUCTURAL
 PLANS FOR LOCATION OF UNITS, PLEASE NOTE THE STRUCTURAL
 PLANS DO NOT PROVIDE ANY ADDITIONAL INFORMATION ON THE
 ROOF TOP UNITS AND OR ADDITIONAL LOADING OR BRACING OF
 THE STRUCTURAL FRAMING OF THE ROOFING SYSTEM.
 ADDITIONAL INFORMATION REQUIRED.106.1.2.
  
 4) SHEET S-1 DETAIL 4& 5 BOTH OF THESE DETAILS ARE NOT
 REFLECTED AAS TO WHERE THEY ARE TO BE DESIGNED IT
 APPEARS THAT STRUCTURAL DETAIL # 1 IS MISSING
 INDICATING THE LOCATION FOR THESE SECTIONS. 106.1.2
 ADDTIONAL INFORMATION IS REQUIED.
  
 5) SHEET S-2 DETAILS 2,3 & 4 FOR STEEL COLUMNS, ALL 3
 COLUMN INDICATE THE TYPE OF WELDS ARE TO BE USED FROM
 THE BOTTOM PLATE TO COLUMN BUT ARE MISSING FROM THE
 COLUMN TO THE TOP PLATE. NOR IS INFORMATION PROVIDED
 FOR THE CONNECTING OF SYSTEM.
  
 6) SHEET S-3 DETAIL# 1 INDICATES THE USE OF GALVANIZED
 WIRE LATH W/ 7/8 INCH STUCCO, PLEASE BE AWARE OF A
 CHANGE IN THE CODE THIS LAST CODE CYCLE:
 1404.2.1 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED
 TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL BE
 TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER AND
 THE WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER OR
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 7) SHEET S-3 DETAIL# 1 DOES NOT INDICATE THE TYPE OF
 WALL SHEATHING TO BE INSTALLED ON THE BACK SIDE OF THE
 DETAIL ONLY FLASHING. FBC-B 1403.3 STRUCTURAL. EXTERIOR
 WALLS, AND THE ASSOCIATED OPENINGS, SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST SAFELY THE SUPERIMPOSED LOADS
 REQUIRED BY CHAPTER 16.1604.9 COUNTERACTING STRUCTURAL
 ACTIONS. STRUCTURAL MEMBERS, SYSTEMS, COMPONENTS AND
 CLADDING SHALL BE DESIGNED TO RESIST FORCES DUE TO
 WIND, WITH CONSIDERATION OF OVERTURNING, SLIDING, AND
 UPLIFT. CONTINUOUS LOAD PATHS SHALL BE PROVIDED FOR
 TRANSMITTING THESE FORCES TO THE FOUNDATION.
  
 8) SHEETS S-5 & S-6 WILL NOT BE REVIEWED AS PART OF
 THIS PERMIT. SIGNS REQUIRE A SEPARATE PERMIT AND THESE
 SHEETS WILL BE REVIEWED WHEN THE SIGN PERMIT HAS BEEN
 SUBMITTED FOR REVIEW.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved