Plan Review Notes
Plan Review Notes For Permit 10090352
Permit Number 10090352
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-09-16 13:28:20THE SLADE CONDOMINIUM
 1551 NORTH FLAGLER DRIVE
 PERMIT NUMBER 10090352
  
  
 1. THE CALL-OUT LINES ARE DIFFICULT TO PINPOINT ON THE
 DRAWING. THE PERMIT DESCRIPTION INDICATES "INSTALL 4
 FIRE ALARM RELAYS TO TIE INTO CARD ACCESS DOOR POWER
 SUPPLIED FOR RELEASE UPON ALARM. (2 ON THE 5TH FLOOR &
 2 ON 9TH FLOOR)
  
 2. WHAT DOORS DO THESE RELAYS CONTROL. ARE EXIT DOORS
 OR NON EXIT DOORS IMPACTED. PLEASE INDICATE WHAT DOORS
 ARE IMPACTED.
  
 3. NOTES ON PAGE 3 INDICATES INFORMATION FOR ACCESS
 CONTROLLED EGRESS DOORS HOWEVER THE PLANS DO NOT
 INDICATE THAT EXIT DOORS ARE INVOLVED.
  
 4. ARE ANY EXISTING DOORS CURRENTLY EQUIPPED WITH THIS
 EQUIPMENT.
  
 5. PLEASE PROVIDE MORE RELEVANT INFORMATION REGARDING
 THIS INSTALLATION.
  
  
 DENIED
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION