| Plan Review Notes For Permit 10090352 |
| Permit Number |
10090352 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-16 13:28:20 | THE SLADE CONDOMINIUM | | | 1551 NORTH FLAGLER DRIVE | | | PERMIT NUMBER 10090352 | | | | | | | | | 1. THE CALL-OUT LINES ARE DIFFICULT TO PINPOINT ON THE | | | DRAWING. THE PERMIT DESCRIPTION INDICATES "INSTALL 4 | | | FIRE ALARM RELAYS TO TIE INTO CARD ACCESS DOOR POWER | | | SUPPLIED FOR RELEASE UPON ALARM. (2 ON THE 5TH FLOOR & | | | 2 ON 9TH FLOOR) | | | | | | 2. WHAT DOORS DO THESE RELAYS CONTROL. ARE EXIT DOORS | | | OR NON EXIT DOORS IMPACTED. PLEASE INDICATE WHAT DOORS | | | ARE IMPACTED. | | | | | | 3. NOTES ON PAGE 3 INDICATES INFORMATION FOR ACCESS | | | CONTROLLED EGRESS DOORS HOWEVER THE PLANS DO NOT | | | INDICATE THAT EXIT DOORS ARE INVOLVED. | | | | | | 4. ARE ANY EXISTING DOORS CURRENTLY EQUIPPED WITH THIS | | | EQUIPMENT. | | | | | | 5. PLEASE PROVIDE MORE RELEVANT INFORMATION REGARDING | | | THIS INSTALLATION. | | | | | | | | | DENIED | | | | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|