| 2010-09-15 13:21:08 | *****REVIEW COMMENTS - FIRE***** |
| | |
| | 1) THE ADDRESS IN THE TITLEBLOCK SHOWS "407 NORTHWOOD |
| | ROAD", THE ADDRESS ON THE PERMIT READS "409 NORTHWOOD |
| | ROAD" AND THE ADDRESS ASSOCIATED WITH THE PARCEL ID ON |
| | THE PERMIT APPLICATION CORRESPONDS TO "401 NORTHWOOD |
| | ROAD." |
| | |
| | 2) WORK SHALL CONFORM TO THE 2002 EDITION OF NFPA 13. |
| | |
| | 3) INCOMING SPRINKLER SERVICE APPEARS TO ENTER IN AN |
| | ELECTRICAL ROOM. |
| | |
| | 4) INDICATE LOCATION OF EXISTING FIRE DEPARTMENT |
| | CONNECTION, CONTROL VALVES, FLOW SWITCH AND TAMPER |
| | SWITCHES. |
| | |
| | 5) INDICATE IF ANY ADJACENT TENANTS SPACES ARE IMPACTED |
| | BY THE SPRINKLER SYSTEM SHUTDOWN. |
| | |
| | 6) PROVIDE SPRINKLER PROTECTION FOR OUTDOOR DINING AREA |
| | COVERED BY AWNING. |
| | |
| | 7) PROVIDE HYDRAULIC CALCULATIONS FOR NEW LAYOUT. |
| | |
| | 8) PROTECT KITCHEN AREA AS ORDINARY HAZARD OCCUPANCY. |
| | |
| | 9) TWO SPRINKLERS IN KITCHEN AREA CURRENTLY LOCATED |
| | MORE THAN 7'-6" FROM WALL. |
| | |
| | 10) PROTECT WALK-IN COOLER WITH DRY PENDENT SPRINKLERS. |
| | |
| | 11) SPRINKLER IN "WAREWASH" LOCATED MORE THAN 7'-6" |
| | FROM WALL. |
| | |
| | 12) VERIFY SPRINKLER PROTECTION IN REGARDS TO RESTROOM |
| | PARTITION HEIGHTS. |
| | |
| | 13) NO SPRINKLER PROTECTION SHOWN FOR SMALL ELECTRICAL |
| | CLOSET ADJACENT TO MEN'S RESTROOM. |
| | |
| | 14) SPRINKLER SPRAY OBSTRUCTED BY WING WALL IN "WAIT |
| | STATION." |
| | |
| | 15) SPRINKLER SPRAY OBSTRUCTED NEAR MAIN ENTRY HOSTESS |
| | STAND. |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | & WESLEY JOLIN |
| | WPB FIRE PLAN REVIEW |