| Plan Review Notes For Permit 10090318 |
| Permit Number |
10090318 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-15 14:03:51 | 524 DATURA STREET | | | PERMIT NUMBER 10090318 | | | INSTALL FIRE ALARM SYSTEM (SPRINKLER MONITORING ONLY) | | | | | | | | | 1. THE FIRE SPRINKLER SYSTEM CONTROL VALVE IS TO BE | | | CHAINED AND LOCKED IN THE "OPEN" POSITION. IT HAS BEEN | | | REPORTED THAT A TAMPER SWITCH CANNOT BE INSTALLED DUE | | | TO THE CURRENT INSTALLATION. | | | | | | 2. THE FIRE ALARM SYSTEM IS TO PROVIDE A WATERFLOW, | | | GENERAL ALARM, AND A TROUBLE CONDITION. | | | | | | 3. AFTER INSTALLATION, SYSTEM IS TO BE TESTED WITH THIS | | | OFFICE. | | | | | | 4. INSTALLATION TO CONFORM TO NFPA 72, THE NATIONAL | | | FIRE ALARM CODE. | | | | | | | | | APPROVED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|