| Plan Review Notes For Permit 10090281 |
| Permit Number |
10090281 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2010-12-21 17:04:03 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE ENERGY CALCULATIONS. PRESCRIPTIVE FORM | | | 1100B-08 SUBMITTED REQUIRES MIN. R30 CEILING | | | INSULATION. | | | | | | 2- REVISE STORM SHUTTERS INSTALLATION SCHEDULE: REVISE | | | SHUTTER SPAN. SHUTTER INSTALLATION IS VERTICAL NOT | | | HORIZONTAL. ANCHOR TYPE TO MATCH ANCHOR SHOWN ON | | | SHUTTERS DRAWINGS. | | | | | | 3- SHEET A-2.0: REVISE COMPONENT AND CLADDING PRESSURE | | | ZONES SPECIFICATIONS TO MATCH PLYWOOD ROOF SHEATHING | | | NOTE "C". | | | |
|