| Plan Review Notes For Permit 10090270 |
| Permit Number |
10090270 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-15 11:23:47 | *****REVIEW COMMENTS - FIRE***** | | | | | | 1) SUITE #50: IN SPACES WHERE ENTIRE ROOM IS NOT | | | COMPLETELY RENOVATED, SHOW EXISTING SPRINKLERS LOCATED | | | ADJACENT TO NEW SPRINKLERS SO ADEQUATE COVERAGE IS | | | DOCUMENTED. | | | | | | 2) NOTE THE THERMAL RESPONSE (QR/SR) IN THE SPRINKLER | | | LEGEND. | | | | | | 3) WORK SHALL CONFORM TO THE 2002 EDITION OF NFPA 13. | | | | | | 4) PROVIDE ADDITIONAL INFORMATION FOR FLEXHEAD DROPS, | | | INCLUDING SIZE (1/2-INCH OR 3/4-INCH), MAXIMUM LENGTH | | | OF FLEXIBLE DROPS, NUMBER OF BENDS PERMITTED AND | | | MINIMUM RADIUS OF BENDS ALLOWED. | | | | | | 5) DOES THE ADDITIONAL FRICTION LOSS OF THE FLEXIBLE | | | DROPS AFFECT THE EXSITING BRANCH LINE AND ARMOVER PIPE | | | SIZING? | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | WPB FIRE PLAN REVIEW | | | 561-805-6730 |
|