| Plan Review Notes For Permit 10090241 |
| Permit Number |
10090241 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-14 17:11:20 | *****REVIEW COMMENTS - FIRE***** | | | | | | 1) SUITE NUMBER ON PLANS DOES NOT MATCH SUITE NUMBER ON | | | PERMIT APPLICATION. | | | | | | 2) WORK SHALL CONFORM TO THE 2002 EDITION OF NFPA 13. | | | | | | 3) CLARIFY NOTE "CEILINGS EXPOSED TO DECK" AS | | | OBSTRUCTED OR UNOBSTRUCTED CONSTRUCTION. | | | | | | 4) NO INFORMATION GIVEN ON NEW PIPE/TUBE TYPE. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | WPB FIRE PLAN REVIEW | | | 561-805-6730 |
|