| Plan Review Notes For Permit 10090234 |
| Permit Number |
10090234 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-01 10:42:55 | FBC 2007 PLUMBING PLAN REVIEW | | | DENIED: | | | | | | 1. IN THE WOMENS RESTROOM THE 3 WC'S FORM A CURCUIT | | | VENT. A DRY VENT IS REQUIRED BETWEEN THE LAST 2 WC'S. | | | 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION | | | SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE | | | DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH | | | AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905. | | | THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE | | | OF ANY SOIL OR WASTE. | | | | | | 2. THE LOUNGE SINK WASTE & VENT IS NOT SHOWN ON THE | | | SANITARY RISER DIAGRAM. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|