2010-10-01 10:42:55FBC 2007 PLUMBING PLAN REVIEW
 DENIED:
  
 1. IN THE WOMENS RESTROOM THE 3 WC'S FORM A CURCUIT
 VENT. A DRY VENT IS REQUIRED BETWEEN THE LAST 2 WC'S.
 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE
 DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905.
 THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE
 OF ANY SOIL OR WASTE.
  
 2. THE LOUNGE SINK WASTE & VENT IS NOT SHOWN ON THE
 SANITARY RISER DIAGRAM.
  