Plan Review Notes
Plan Review Notes For Permit 10090217
Permit Number 10090217
Review Stop B
Sequence Number 1
Notes
Date Text
2010-09-13 18:49:41****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE PAGE 26 OF THE PRODUCT APPROAL. 6" ANCHOR
 SPACING REQUIRED FOR 1/4" TAPCONS, 10" FOR 5/16"
 TAPCONS. INSTALLATION SCHEDULE SPECIFIES ITW 1/4", 10"
 SPACING FOR THE BOTTOM. EITHER REVISE SPACING OR REVISE
 ANCHOR TO COMPLY WITH REQUIREMENTS OF THE PRODUCT
 APPROVAL.
  