| 2010-09-17 09:48:50 | PURE VIDA |
| | 700 SOUTH ROSEMARY AVENUE |
| | PERMIT NUMBER 10090192 |
| | |
| | |
| | 1. ON SHEET A-0.0 IN THE CODE PROJECT DESIGN BOX BB |
| | KINGS, 550 SOUTH ROSEMARY AVENUE IS LISTED HOWEVER THE |
| | DRAWINGS INDICATES THE ADDRESS OF 700 SOUTH ROSEMARY |
| | AVENUE. |
| | |
| | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEM INSTALLATIONS AND |
| | REMODELS. |
| | |
| | 3. CROWD MANAGEMENT TRAINING WILL BE REQUIRED FOR |
| | SELECTED STAFF. PLEASE GO TO WWW.MARYLAND STATE FIRE |
| | MARSHALS WEB-SITE AND CLICK ON THE CROWD MANAGEMENT |
| | TRAINING ICON, WATCH THE VIDEO, AND TAKE THE TEST. |
| | COPIES OF CERTIFICATES ARE TO BE SUBMITTED TO THE FIRE |
| | MARSHALS OFFICE PRIOR TO OPENING. OVERCROWDING IS NOT |
| | PERMITTED WITHIN THE ESTABLISHMENT. THE FINAL OCCUPANT |
| | LOAD IS TO BE DETERMINED BY THIS OFFICE. THE FINAL |
| | OCCUPANT LOAD IS TO BE POSTED WITHIN THE ESTABLISHMENT. |
| | WHEN OPENED, PERSONS ARE TO BE CLICKED IN AND OUT TO |
| | ENSURE THAT THE MAXIMUM OCCUPANT LOAD IS FOLLOWED. |
| | |
| | 4. THE LOUNGE/ SEATING AREA 105 APPEARS CROWDED. PLEASE |
| | REVIEW THIS AREA FOR AQEQUATE EXIT ACCESS. |
| | |
| | 5. ALL RATED FIRE DOORS ARE TO BE EQUIPPED WITH RATED |
| | PANIC HARDWARE. |
| | |
| | 6. ALL COOLERS AND FREEZERS ARE TO BE FIRE SPRINKLER |
| | PROTECTED. |
| | |
| | 7. PLEASE INDICATE WHAT THE VOICE EVACUATION PORTION OF |
| | THE FIRE ALARM SYSTEM WILL INDICATE WHEN ACTIVATED. |
| | |
| | 8. ALL FIRE WALL PENTRATIONS ARE TO BE PROPERLY SEALED |
| | IN AN APPROVED MANNER WITH APPROVED MATERIALS. |
| | |
| | 9. ALL EXISTING FIRE WALLS SHALL BE IN GOOD CONDITION. |
| | |
| | 10. PANIC HARDWARE SHALL BE PROVIDED ON EXIT DOORS. |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |