| 2010-09-16 15:20:04 | PURE VIDA |
| | 700 SOUTH ROSEMARY AVENUE |
| | PERMIT NUMBER 10090192 |
| | |
| | |
| | 1. ON SHEET A-1.0 IN THE CODE /PROJECT DESIGN BOX IT |
| | REFERENCES BB KINGS, 550 SOUTH ROSEMARY AVENUE BUT THE |
| | PLANS ILLUSTRATE A TENANT SPACE AT 700 SOUTH ROSEMARY |
| | AVENUE. |
| | |
| | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEM INSTALLATIONS AND |
| | REMODELS. |
| | |
| | 3. SINCE THE OCCUPANT LOAD IS EXPECTED TO BE ABOVE 250 |
| | PERSONS CROWD MANAGEMENT TRAINING IS REQUIRED. PLEASE |
| | HAVE SELECTED PERSONNEL GO TO WWW.MARYLAND STATE FIRE |
| | MARSHAL'S OFFICE AND CLICK THE CROWD MANAGEMENT ICON. |
| | STAFF MEMBERS ARE TO WATCH THE VIDEO AND TAKE THE TEST. |
| | COPIES OF CERTIFICATES ARE TO BE SUBMITTED TO THE FIRE |
| | MARSHAL'S OFFICE PRIOR TO OPENING. OVERCROWDING IS NOT |
| | PERMITTED WITHIN THE ESTABLISHMENT. THE FINAL OCCUPANT |
| | LOAD WILL BE DETERMINED BY THIS OFFICE AND WILL BE |
| | REQUIRED TO BE POSTED. STAFF MEMBERS ARE TO CLICK IN |
| | AND OUTS TO PREVENT OVERCROWDING. |
| | |
| | 4. ALL RATED FIRE DOORS ARE TO BE EQUIPPED WITH FIRE |
| | RATED PANIC HARDWARE. OTHER EXIT DOORS ARE TO BE |
| | EQUIPPED WITH PANIC HARDWARE. |
| | |
| | 5. IT APPEARS THAT THE LOUNGE/SEATING AREA 105 IS TOO |
| | CROWDED. PLEASE REVIEW AREA TO DETERMINE ADEQUATE EXIT |
| | ACCESS. |
| | |
| | 6. ALL EXISTING FIRE WALLS IF DAMAGED ARE TO BE |
| | REPAIRED TO PREVIOUS CONDITION. ALL PIPE PENETRATIONS |
| | ARE TO BE SEALED IN AN APPROVED MANNER WITH APPROVED |
| | MATERIALS FOR THAT PURPOSE. |
| | |
| | 7. THE FIRE ALARM SYSTEM IS REQUIRED TO PROVIDE VOICE |
| | EVACUATION INSTRUCTIONS TO THE OCCUPANTS UPON |
| | ACTIVATION OF THE FIRE ALARM SYSTEM. PLEASE INDICATE |
| | WHAT THE VOICE EVACUATION PROMPTS WILL INDICATE TO |
| | VISITORS TO DO IN THE EVENT OF AN EMERGENCY. |
| | |
| | 8. ALL COOLERS AND FREEZERS ARE TO BE FIRE SPRINKLER |
| | PROTECTED. |
| | |
| | 9. PLEASE DEMONSTRATE COMPLIANCE WITH FIRE RETARDANT |
| | CRITERIA FOR THE TIKI COVERING MATERIAL SHOWN ON SHEET |
| | A-5.0. |
| | |
| | 10. THE INSTALLATION OF ANY SOFFIT MATERIAL SHALL NOT |
| | INTERFERE WITH THE OPERATION OF ANY FIRE SPRINKLER |
| | HEADS. |
| | |
| | |
| | DENIED |
| | |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |