Plan Review Notes
Plan Review Notes For Permit 10090130
Permit Number 10090130
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2011-02-03 15:37:171810 SOUTH DIXIE HIGHWAY
 PERMIT #10090130
 REVIEW COMMENTS - FIRE
  
 NOTE: THIS IS A CHANGE OF OCCUPANCY FROM INDUSTRIAL TO
 MERCANTILE.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 THE MEZZANINE STAIR IS NOT PERMITTED TO BE OPEN TO BOTH
 LEVELS PER SECTION 36.3.1 OF THE FLORIDA FIRE
 PREVENTION CODE (NFPA 101). INSIDE STAIRS SERVING AS AN
 EXIT COMPONENT SHALL BE ENCLOSED PER SECTION
 7.2.2.5.1.1 OF THE FFPC (NFPA 101).
  
 ENCLOSURE OF THE MEZZANINE OFFICE WILL REQUIRE
 ADDITIONAL EMERGENCY LIGHTING.
  
 PROVIDE STAIR AND HANDRAIL DETAILS. STAIR HANDRAILS ARE
 REQUIRED ON BOTH SIDES OF THE STAIR PER SECTION
 7.2.2.4.1.1 OF THE FFPC (NFPA 101).
  
 PROVIDE DOOR LOCKING AND LATCHING HARDWARE INFORMATION.
  
 AISLES LEADING TO EACH ARE REQUIRED. AISLES SHALL BE AT
 LEAST 36-INCHES IN WIDTH PER SECTION 36.2.5.4 OF THE
 FFPC (NFPA 101).
  
 INTERIOR WALL FINISH TO BE CLASS A OR CLASS B PER
 SECTION 36.3.3.2 OF THE FFPC (NFPA 101).
  
 TRAVEL DISTANCE TO PORTABLE FIRE EXTINGUISHERS NOT TO
 EXCEED 75 FEET.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR FUTURE 4-INCH
 PARTITION WALL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW