| 2011-02-03 15:37:17 | 1810 SOUTH DIXIE HIGHWAY | | | PERMIT #10090130 | | | REVIEW COMMENTS - FIRE | | | | | | NOTE: THIS IS A CHANGE OF OCCUPANCY FROM INDUSTRIAL TO | | | MERCANTILE. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | THE MEZZANINE STAIR IS NOT PERMITTED TO BE OPEN TO BOTH | | | LEVELS PER SECTION 36.3.1 OF THE FLORIDA FIRE | | | PREVENTION CODE (NFPA 101). INSIDE STAIRS SERVING AS AN | | | EXIT COMPONENT SHALL BE ENCLOSED PER SECTION | | | 7.2.2.5.1.1 OF THE FFPC (NFPA 101). | | | | | | ENCLOSURE OF THE MEZZANINE OFFICE WILL REQUIRE | | | ADDITIONAL EMERGENCY LIGHTING. | | | | | | PROVIDE STAIR AND HANDRAIL DETAILS. STAIR HANDRAILS ARE | | | REQUIRED ON BOTH SIDES OF THE STAIR PER SECTION | | | 7.2.2.4.1.1 OF THE FFPC (NFPA 101). | | | | | | PROVIDE DOOR LOCKING AND LATCHING HARDWARE INFORMATION. | | | | | | AISLES LEADING TO EACH ARE REQUIRED. AISLES SHALL BE AT | | | LEAST 36-INCHES IN WIDTH PER SECTION 36.2.5.4 OF THE | | | FFPC (NFPA 101). | | | | | | INTERIOR WALL FINISH TO BE CLASS A OR CLASS B PER | | | SECTION 36.3.3.2 OF THE FFPC (NFPA 101). | | | | | | TRAVEL DISTANCE TO PORTABLE FIRE EXTINGUISHERS NOT TO | | | EXCEED 75 FEET. | | | | | | SEPARATE PLANS AND PERMIT REQUIRED FOR FUTURE 4-INCH | | | PARTITION WALL. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|