| Plan Review Notes For Permit 10090130 |
| Permit Number |
10090130 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-01 14:39:40 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. SHEET 1 SHOWS AN OCCUPANT LOAD OF 50 BUSINESS. TWO | | | RESTROOMS WOULD BE REQUIRED | | | FBC PLUMBING 2007 TABLE 403.1- MINIMUM NUMBER OF | | | REQUIRED PLUMBING FIXTURES- 1 PER 25 FOR THE FIRST 50 | | | AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|