Plan Review Notes
Plan Review Notes For Permit 10090130
Permit Number 10090130
Review Stop P
Sequence Number 1
Notes
Date Text
2010-10-01 14:39:40FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEET 1 SHOWS AN OCCUPANT LOAD OF 50 BUSINESS. TWO
 RESTROOMS WOULD BE REQUIRED
 FBC PLUMBING 2007 TABLE 403.1- MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES- 1 PER 25 FOR THE FIRST 50
 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR