2010-09-28 13:40:491810 SOUTH DIXIE HIGHWAY
 PERMIT NUMBER 10090130
 "BUILDING RENOVATION"
  
  
 1. BUILDING ADDRESS NOT CONTAINED IN THE TITLE BLOCK.
  
 2. ON SHEET 1 IT DECLARES THE LOCATION AS A BUSINESS
 OCCUPANCY. ON SHEET 3 IT STIPULATES "WAREHOUSE
 SHOWROOM". THE FLOOR PLAN SEEMS TO SUGGEST EITHER A
 MERCANTILE OCCUPANCY OR AS A STORAGE OCCUPANCY. PLEASE
 DECLARE CORRECT OCCUPANCY TYPE AND ADJUST OCCUPANT LOAD
 AS BOTH HAVE THESE HAVE DIFFERENT OCCUPANT LOAD FACTORS
 THAN BUSINESS. DOES RETAIL OR WHOLESALES EXCHANGES
 OCCUR AT THE PROPERTY OR ARE MATERIALS STORED AT THE
 LOCATION.
  
 3. BUILDING ADDRESS SHOWN ON PAGE 4. THE BUILDING
 ADDRESS SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT
 LEAST 1" WIDE THAT CONTRASTS WITH THE BACKGROUND THAT
 IS AFFIXED TO.
  
 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 5. THE TWO EMERGENCY LIGHTS DISPLAYED ON SHEET 6B MAY
 NOT BE ADEQUATE DUE TO THE SIZE OF THE SPACE. PLEASE
 EVALUATE FIXTURE COUNT AND LOCATIONS.
  
 6. PLEASE DECLARE ON PLANS THE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 7. PLEASE DECLARE IF EXISTING OR NEW PORTABLE FIRE
 EXTINGUISHERS WILL BE PRESENT.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF