| Plan Review Notes For Permit 10090130 |
| Permit Number |
10090130 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-03 15:36:15 | | | | | | 2010-09-28 13:40:49 | 1810 SOUTH DIXIE HIGHWAY | | | PERMIT NUMBER 10090130 | | | "BUILDING RENOVATION" | | | | | | | | | 1. BUILDING ADDRESS NOT CONTAINED IN THE TITLE BLOCK. | | | | | | 2. ON SHEET 1 IT DECLARES THE LOCATION AS A BUSINESS | | | OCCUPANCY. ON SHEET 3 IT STIPULATES "WAREHOUSE | | | SHOWROOM". THE FLOOR PLAN SEEMS TO SUGGEST EITHER A | | | MERCANTILE OCCUPANCY OR AS A STORAGE OCCUPANCY. PLEASE | | | DECLARE CORRECT OCCUPANCY TYPE AND ADJUST OCCUPANT LOAD | | | AS BOTH HAVE THESE HAVE DIFFERENT OCCUPANT LOAD FACTORS | | | THAN BUSINESS. DOES RETAIL OR WHOLESALES EXCHANGES | | | OCCUR AT THE PROPERTY OR ARE MATERIALS STORED AT THE | | | LOCATION. | | | | | | 3. BUILDING ADDRESS SHOWN ON PAGE 4. THE BUILDING | | | ADDRESS SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT | | | LEAST 1" WIDE THAT CONTRASTS WITH THE BACKGROUND THAT | | | IS AFFIXED TO. | | | | | | 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 5. THE TWO EMERGENCY LIGHTS DISPLAYED ON SHEET 6B MAY | | | NOT BE ADEQUATE DUE TO THE SIZE OF THE SPACE. PLEASE | | | EVALUATE FIXTURE COUNT AND LOCATIONS. | | | | | | 6. PLEASE DECLARE ON PLANS THE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 7. PLEASE DECLARE IF EXISTING OR NEW PORTABLE FIRE | | | EXTINGUISHERS WILL BE PRESENT. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|