Plan Review Notes
Plan Review Notes For Permit 10090130
Permit Number 10090130
Review Stop B
Sequence Number 1
Notes
Date Text
2010-09-28 11:48:03BUILDING PLAN REVIEW
 PERMIT: 10090130
 ADD: 1810 S DIXIE HWY
 CONT: MARTINO CONSTRUCTION
 TEL: (561)632-2338
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 BUILDING DESIGNOR TYPE: II-B
  
 1) SHEET# 1 WIND LOAD INFORMATION: THE PLANS INDICATE
 THE WIND EXPOSURE AS A B EXPOSURE PLEASE REVIEW FBC-B
 1609.4.2 SURFACE ROUGHNESS CATEGORIES.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS,
 INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES,
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM)
 EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE
 BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
 2) SINCE THIS BUILDING IS LOCATED WITHIN A EXPOSURE C
 LOCATION THE PRESSURES WILL BE GREATER THAN EXPOSURE B
 PLEASE UP DATE PLANS FOR THE GREATER PRESSURES AND
 REVIEW THE PRODUCT APPROVALS FOR THESE PRESSURES.
  
  
 3) SHEET 3 INDICATES A FLOOR PLAN WITH THE TERMINOLOGY
 WAREHOUSE SHOWROOM PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
 3A) PLEASE PROVIDE AS TO WHAT OCCUPANCY CLASSIFICATION
 THIS TENANCY WAS DESIGNED TOO, FBC-B2009
 SUPPLEMENTS.302.1 GENERAL. STRUCTURES OR PORTIONS OF
 STRUCTURES SHALL BE CLASSIFIED WITH RESPECT TO
 OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW. A
 ROOM OR SPACE THAT IS INTENDED TO BE OCCUPIED AT
 DIFFERENT TIMES FOR DIFFERENT PURPOSES SHALL COMPLY
 WITH ALL OF THE REQUIREMENTS THAT ARE APPLICABLE TO
 EACH OF THE PURPOSES FOR WHICH THE ROOM OR SPACE WILL
 BE OCCUPIED. FOR THIS REVIEW THE OCCUPANCY SHALL BE
 CONSIDERED MERCANTILE. PLEASE EXPLAIN HOW THIS IS A
 BUSINESS OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A
 BUILDING OR STRUCTURE, OR A PORTION THEREOF, FOR
 OFFICE, PROFESSIONAL OR SERVICE-TYPE TRANSACTIONS,
 INCLUDING STORAGE OF RECORDS AND ACCOUNTS.FBC-B 304.1.
  
 3B) PLEASE SHOW OCCUPANCY LOAD PER FBC-B TABLE
 1004.1.1.
  
 3C) THE PLANS DO NOT INDICATE A LIFE SAFETY PLAN,
 PLEASE SHOW ON SHEET# 3 THE ACTUAL FLOOR PLAN WITH
 GOODS BEING DISPLAYED,STORED AND SOLD AS WELL AS THE
 DEFINED EGRESS PATH. FBC-B 309.1, & FBC-B 1014.4.1 &
 1014.4.2.
  
 3D) THE PLANS DO NOT INDICATE IF THIS BUILDING IS FIRE
 SPRINKLERED?
  
 4) SHEET # 3 INDICATES OVER THE EXISTING OFFICE THE
 RESTROOM TO BE REMOVED PLEASE INDICATE WHAT OCCUPANCY
 WILL OCCUPY THIS ROOM?FBC-B 302.1.
  
 5) SHEET# 5 DETAIL 5-2 INDICATES THE USE OF 5 1/2
 INCHES OF SPRAY ON FOAM ONTO THE BOTTOM SIDE OF THE
 TWIN T'S. PLEASE PROVIDE COMPLIANCE WITH FBC-B 2603.4
 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN SECTIONS
 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE SEPARATED
 FROM THE INTERIOR OF A BUILDING BY AN APPROVED THERMAL
 BARRIER OF 0.5-INCH (12.7 MM) GYPSUM WALLBOARD OR
 EQUIVALENT THERMAL BARRIER MATERIAL THAT WILL LIMIT THE
 AVERAGE TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO
 NOT MORE THAN 250??F (120??C) AFTER 15 MINUTES OF FIRE
 EXPOSURE, COMPLYING WITH THE STANDARD TIME-TEMPERATURE
 CURVE OF ASTM E 119. THE THERMAL BARRIER SHALL BE
 INSTALLED IN SUCH A MANNER THAT IT WILL REMAIN IN PLACE
 FOR 15 MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR
 UL 1715. COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH
 SECTION 717. NOTE THIS IS ALSO LABELED A TYPE II-B
 BUILDING NEEDING TO MEET THE CRITERIA FOUND UNDER FBC-B
 603.1.
  
 6) SHEET #5 EXTERIOR WALL METAL FRAME IN-FILL WALL
 SECTIONS INDICATE THE USE OF PLYWOOD SHEATHING, PLEASE
 REVIEW FBC-B SECTION 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR TYPE II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
  
 7) SHEET #5 EXTERIOR METAL WALL FRAME SECTION
 INDICATING THE USE OF RIB LATH AND STUCCCO, PLEASE
 REVIEW THIS NEW CHANGE IN THE 2007 FBC-B 1404.2.1.
  
 8) SHEET# 5 SECTION 3 & 5 ARE MISSING THE INSULATION TO
 THE ROOF LINE PER 11-13-402.A REQUIREMENTS SPECIFIC TO
 METHOD A. EFFICIENCIES DETERMINED BY THE ENERGYGAUGE
 SUMMIT FLA/COM METHOD A PERFORMANCE CALCULATION TO
 DEMONSTRATE COMPLIANCE WITH THIS CODE SHALL BE THE
 MINIMUM PERFORMANCE LEVEL INSTALLED IN WALLS. R-4
 INSULATION AND 1/2 INCH GYPSUM BOARD.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved