| 2010-09-28 11:48:03 | BUILDING PLAN REVIEW |
| | PERMIT: 10090130 |
| | ADD: 1810 S DIXIE HWY |
| | CONT: MARTINO CONSTRUCTION |
| | TEL: (561)632-2338 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | BUILDING DESIGNOR TYPE: II-B |
| | |
| | 1) SHEET# 1 WIND LOAD INFORMATION: THE PLANS INDICATE |
| | THE WIND EXPOSURE AS A B EXPOSURE PLEASE REVIEW FBC-B |
| | 1609.4.2 SURFACE ROUGHNESS CATEGORIES. |
| | EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS, |
| | INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES, |
| | HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM) |
| | EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE |
| | BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO |
| | APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE |
| | TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET |
| | HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE |
| | C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9 |
| | M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND |
| | DIRECTION. |
| | |
| | 2) SINCE THIS BUILDING IS LOCATED WITHIN A EXPOSURE C |
| | LOCATION THE PRESSURES WILL BE GREATER THAN EXPOSURE B |
| | PLEASE UP DATE PLANS FOR THE GREATER PRESSURES AND |
| | REVIEW THE PRODUCT APPROVALS FOR THESE PRESSURES. |
| | |
| | |
| | 3) SHEET 3 INDICATES A FLOOR PLAN WITH THE TERMINOLOGY |
| | WAREHOUSE SHOWROOM PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION: |
| | 3A) PLEASE PROVIDE AS TO WHAT OCCUPANCY CLASSIFICATION |
| | THIS TENANCY WAS DESIGNED TOO, FBC-B2009 |
| | SUPPLEMENTS.302.1 GENERAL. STRUCTURES OR PORTIONS OF |
| | STRUCTURES SHALL BE CLASSIFIED WITH RESPECT TO |
| | OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW. A |
| | ROOM OR SPACE THAT IS INTENDED TO BE OCCUPIED AT |
| | DIFFERENT TIMES FOR DIFFERENT PURPOSES SHALL COMPLY |
| | WITH ALL OF THE REQUIREMENTS THAT ARE APPLICABLE TO |
| | EACH OF THE PURPOSES FOR WHICH THE ROOM OR SPACE WILL |
| | BE OCCUPIED. FOR THIS REVIEW THE OCCUPANCY SHALL BE |
| | CONSIDERED MERCANTILE. PLEASE EXPLAIN HOW THIS IS A |
| | BUSINESS OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A |
| | BUILDING OR STRUCTURE, OR A PORTION THEREOF, FOR |
| | OFFICE, PROFESSIONAL OR SERVICE-TYPE TRANSACTIONS, |
| | INCLUDING STORAGE OF RECORDS AND ACCOUNTS.FBC-B 304.1. |
| | |
| | 3B) PLEASE SHOW OCCUPANCY LOAD PER FBC-B TABLE |
| | 1004.1.1. |
| | |
| | 3C) THE PLANS DO NOT INDICATE A LIFE SAFETY PLAN, |
| | PLEASE SHOW ON SHEET# 3 THE ACTUAL FLOOR PLAN WITH |
| | GOODS BEING DISPLAYED,STORED AND SOLD AS WELL AS THE |
| | DEFINED EGRESS PATH. FBC-B 309.1, & FBC-B 1014.4.1 & |
| | 1014.4.2. |
| | |
| | 3D) THE PLANS DO NOT INDICATE IF THIS BUILDING IS FIRE |
| | SPRINKLERED? |
| | |
| | 4) SHEET # 3 INDICATES OVER THE EXISTING OFFICE THE |
| | RESTROOM TO BE REMOVED PLEASE INDICATE WHAT OCCUPANCY |
| | WILL OCCUPY THIS ROOM?FBC-B 302.1. |
| | |
| | 5) SHEET# 5 DETAIL 5-2 INDICATES THE USE OF 5 1/2 |
| | INCHES OF SPRAY ON FOAM ONTO THE BOTTOM SIDE OF THE |
| | TWIN T'S. PLEASE PROVIDE COMPLIANCE WITH FBC-B 2603.4 |
| | THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN SECTIONS |
| | 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE SEPARATED |
| | FROM THE INTERIOR OF A BUILDING BY AN APPROVED THERMAL |
| | BARRIER OF 0.5-INCH (12.7 MM) GYPSUM WALLBOARD OR |
| | EQUIVALENT THERMAL BARRIER MATERIAL THAT WILL LIMIT THE |
| | AVERAGE TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO |
| | NOT MORE THAN 250??F (120??C) AFTER 15 MINUTES OF FIRE |
| | EXPOSURE, COMPLYING WITH THE STANDARD TIME-TEMPERATURE |
| | CURVE OF ASTM E 119. THE THERMAL BARRIER SHALL BE |
| | INSTALLED IN SUCH A MANNER THAT IT WILL REMAIN IN PLACE |
| | FOR 15 MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR |
| | UL 1715. COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH |
| | SECTION 717. NOTE THIS IS ALSO LABELED A TYPE II-B |
| | BUILDING NEEDING TO MEET THE CRITERIA FOUND UNDER FBC-B |
| | 603.1. |
| | |
| | 6) SHEET #5 EXTERIOR WALL METAL FRAME IN-FILL WALL |
| | SECTIONS INDICATE THE USE OF PLYWOOD SHEATHING, PLEASE |
| | REVIEW FBC-B SECTION 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR TYPE II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| | FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| | 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS |
| | REQUIRED. |
| | |
| | 7) SHEET #5 EXTERIOR METAL WALL FRAME SECTION |
| | INDICATING THE USE OF RIB LATH AND STUCCCO, PLEASE |
| | REVIEW THIS NEW CHANGE IN THE 2007 FBC-B 1404.2.1. |
| | |
| | 8) SHEET# 5 SECTION 3 & 5 ARE MISSING THE INSULATION TO |
| | THE ROOF LINE PER 11-13-402.A REQUIREMENTS SPECIFIC TO |
| | METHOD A. EFFICIENCIES DETERMINED BY THE ENERGYGAUGE |
| | SUMMIT FLA/COM METHOD A PERFORMANCE CALCULATION TO |
| | DEMONSTRATE COMPLIANCE WITH THIS CODE SHALL BE THE |
| | MINIMUM PERFORMANCE LEVEL INSTALLED IN WALLS. R-4 |
| | INSULATION AND 1/2 INCH GYPSUM BOARD. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |