| Plan Review Notes For Permit 10090113 |
| Permit Number |
10090113 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-14 13:54:45 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE A FLOOR PLAN WHICH SHOWS WINDOW LOCATIONS, | | | SIZES, AND MANUFACTURER (TWO DIFFERENT WINDOW PRODUCT | | | APPROVALS SUBMITTED), FBC R301. | | | | | | 2. THE PRODUCT APPROVALS PROVIDED ARE EXPIRED. PROVIDE | | | A CURRENT FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | FAC9B72. | | | | | | 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM | | | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) | | | | | | |
|