2010-10-05 16:00:17ELECTRICAL PLAN REVIEW
 PERMIT: 10090080
 ADD: 926 SUNSET RD
 CONT: O/B MARIA GEORGE
 TEL: (561)718-4600
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2008 NEC
  
 SHED PERMIT: 2578J 18 FT X 18 FT 11-1-84 ORIGINAL
 PERMIT FOR SHED.
  
 THIS REVIEW WILL USE THE 2007 EXISTING BUILDING CODE
 CHAPTER 9 CHANGE IN OCCUPANCY FOR THE BASIS OF THIS
 REVIEW. EX. BLDG CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 EX. BLDG CODE 903.1 GENERAL. BUILDING ELEMENTS AND
 MATERIALS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE
 OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 912.
  
  
 1ST REVIEW
 ACTION: DENIED
 1) EX. BLDG CODE 908.2 UNSAFE CONDITIONS. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED, ALL UNSAFE CONDITIONS
 SHALL BE CORRECTED WITHOUT REQUIRING THAT ALL PARTS OF
 THE ELECTRICAL SYSTEM BE BROUGHT UP TO THE CURRENT
 EDITION OF CHAPTER 27 OF THE FLORIDA BUILDING CODE,
 BUILDING .
  
 1A) PLEASE PROVIDE LOAD CALCULATIONS PER2008 NEC 220.
 I-IV .
  
  
 1B) 2008 NEC- NEW ARC-FAULT PROTECTION IS NOW REQUIRED
 IN RESIDENTIAL OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH
 CIRCUITS THAT ARE NOT ALREADY REQUIRED TO BE PROTECTED
 BY GROUND FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER
 120 VOLTS 2110.12(B)
  
 1C) 2008 NEC-NEW MULTI-WIRE BRANCH CIRCUITS THAT SHARE
 A COMMON GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON
 DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE
 SAME TIME 210.4(B).
  
 1D) KITCHEN CABINETRY GFIC OUTLET (E3), PLEASE PROVIDE
 COMPLIANCE WITH 210.11(C)(1) SMALL-APPLIANCE BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, TWO OR MORE
 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE
 PROVIDED FOR ALL RECEPTACLE OUTLETS SPECIFIED BY
 210.52(B).
 REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D), 21011.C.3
  
 1E) BATHROOM GFIC OUTLET PLANS FAIL TO INDICATE
 COMPLIANCE WITH SECTION 210.11 (C)(3) BATHROOM BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS.
  
 1F) UTILITY ROOM CIRCUIT IS NOT SHOWN ON PLANS
 REQUIRING A GFCI CIRCUIT. 210.8(C)(2) LAUNDRY BRANCH
 CIRCUIT. LAUNDRY/ WASHER PLEASE REVIEW 210.52, 210.11C2
 & 220.52.3
  
 1G) LAUNDRY BRANCH CIRCUITS: LAUNDRY BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE ADDITIONAL
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 THE LAUNDRY RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F).
 THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS.
  
 1H) . DRYER OUTLET.220.54 ELECTRIC CLOTHES DRYERS ???
 DWELLING UNIT(S)
 THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES DRYERS IN A
 DWELLING UNIT(S) SHALL BE EITHER 5000 WATTS
 (VOLT-AMPERES) OR THE NAMEPLATE RATING, WHICHEVER IS
 LARGER, FOR EACH DRYER SERVED.
  
 1I) A POSSIBLE CONDITION. EXISTING BUILDING CODE/ LEVEL
 2/ 708.3.7.2 REPLACEMENT RECEPTACLES. FOR REPLACEMENT
 OF NONGROUNDING-TYPE RECEPTACLES WITH GROUNDING-TYPE
 RECEPTACLES AND FOR BRANCH CIRCUITS THAT DO NOT HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR IN THE BRANCH CIRCUITRY,
 THE GROUNDING CONDUCTOR OF A GROUNDING-TYPE RECEPTACLE
 OUTLET SHALL BE PERMITTED TO BE GROUNDED TO ANY
 ACCESSIBLE POINT ON THE GROUNDING ELECTRODE SYSTEM, OR
 TO ANY ACCESSIBLE POINT ON THE GROUNDING ELECTRODE
 CONDUCTOR, IN ACCORDANCE WITH ARTICLE 250.130(C) OF
 CHAPTER 27 OF THE FLORIDA BUILDING CODE, BUILDING
  
 1J) THE BEDROOM DOES INDICATE A SMOKE ALARM WITHIN THE
 UNIT OR ONE OUTSIDE OF THE BEDROOM. FBC RESIDENTIAL
 313.2(2) AND NFPA 72.
 THE SMOKE ALARMS LOCATED WITHIN 20' OF COOKING WILL
 NEED TO BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE
 ALARMS AND SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20
 FT) HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
  
 2) 908.4 NUMBER OF ELECTRICAL OUTLETS. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED, THE NUMBER OF ELECTRICAL
 OUTLETS SHALL COMPLY WITH CHAPTER 27 OF THE FLORIDA
 BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY.
 2008 NEC 210.50(A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE OUTLET.
  
 2008 NEC 210.50(A)(2)(1) ANY SPACE 2 FEET OR MORE IN
 WIDTH (INCLUDING SPACE MEASURED AROUND CORNERS) AND
 UNBROKEN ALONG THE FLOOR LINE BY DOORS, FIREPLACES, AND
 SIMILAR OPENINGS.
 2A) THE BEDROOM WALL COMMON WITH THE LIVING ROOM.
  
 2B) THE LIVING ROOM WALL LEFT OF THE ENTRY DOOR.
  
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved