| 2010-10-05 16:00:17 | ELECTRICAL PLAN REVIEW |
| | PERMIT: 10090080 |
| | ADD: 926 SUNSET RD |
| | CONT: O/B MARIA GEORGE |
| | TEL: (561)718-4600 |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | 2008 NEC |
| | |
| | SHED PERMIT: 2578J 18 FT X 18 FT 11-1-84 ORIGINAL |
| | PERMIT FOR SHED. |
| | |
| | THIS REVIEW WILL USE THE 2007 EXISTING BUILDING CODE |
| | CHAPTER 9 CHANGE IN OCCUPANCY FOR THE BASIS OF THIS |
| | REVIEW. EX. BLDG CODE 901.3 CHANGE OF OCCUPANCY |
| | CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A |
| | BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902 |
| | THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF |
| | OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A |
| | CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A |
| | DIFFERENT GROUP. |
| | |
| | EX. BLDG CODE 903.1 GENERAL. BUILDING ELEMENTS AND |
| | MATERIALS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE |
| | OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION |
| | 912. |
| | |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 1) EX. BLDG CODE 908.2 UNSAFE CONDITIONS. WHERE THE |
| | OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN |
| | EXISTING BUILDING IS CHANGED, ALL UNSAFE CONDITIONS |
| | SHALL BE CORRECTED WITHOUT REQUIRING THAT ALL PARTS OF |
| | THE ELECTRICAL SYSTEM BE BROUGHT UP TO THE CURRENT |
| | EDITION OF CHAPTER 27 OF THE FLORIDA BUILDING CODE, |
| | BUILDING . |
| | |
| | 1A) PLEASE PROVIDE LOAD CALCULATIONS PER2008 NEC 220. |
| | I-IV . |
| | |
| | |
| | 1B) 2008 NEC- NEW ARC-FAULT PROTECTION IS NOW REQUIRED |
| | IN RESIDENTIAL OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH |
| | CIRCUITS THAT ARE NOT ALREADY REQUIRED TO BE PROTECTED |
| | BY GROUND FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER |
| | 120 VOLTS 2110.12(B) |
| | |
| | 1C) 2008 NEC-NEW MULTI-WIRE BRANCH CIRCUITS THAT SHARE |
| | A COMMON GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON |
| | DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE |
| | SAME TIME 210.4(B). |
| | |
| | 1D) KITCHEN CABINETRY GFIC OUTLET (E3), PLEASE PROVIDE |
| | COMPLIANCE WITH 210.11(C)(1) SMALL-APPLIANCE BRANCH |
| | CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| | REQUIRED BY OTHER PARTS OF THIS SECTION, TWO OR MORE |
| | 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE |
| | PROVIDED FOR ALL RECEPTACLE OUTLETS SPECIFIED BY |
| | 210.52(B). |
| | REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D), 21011.C.3 |
| | |
| | 1E) BATHROOM GFIC OUTLET PLANS FAIL TO INDICATE |
| | COMPLIANCE WITH SECTION 210.11 (C)(3) BATHROOM BRANCH |
| | CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| | REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| | 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| | BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| | NO OTHER OUTLETS. |
| | |
| | 1F) UTILITY ROOM CIRCUIT IS NOT SHOWN ON PLANS |
| | REQUIRING A GFCI CIRCUIT. 210.8(C)(2) LAUNDRY BRANCH |
| | CIRCUIT. LAUNDRY/ WASHER PLEASE REVIEW 210.52, 210.11C2 |
| | & 220.52.3 |
| | |
| | 1G) LAUNDRY BRANCH CIRCUITS: LAUNDRY BRANCH CIRCUITS IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, AT LEAST ONE ADDITIONAL |
| | 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| | THE LAUNDRY RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). |
| | THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS. |
| | |
| | 1H) . DRYER OUTLET.220.54 ELECTRIC CLOTHES DRYERS ??? |
| | DWELLING UNIT(S) |
| | THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES DRYERS IN A |
| | DWELLING UNIT(S) SHALL BE EITHER 5000 WATTS |
| | (VOLT-AMPERES) OR THE NAMEPLATE RATING, WHICHEVER IS |
| | LARGER, FOR EACH DRYER SERVED. |
| | |
| | 1I) A POSSIBLE CONDITION. EXISTING BUILDING CODE/ LEVEL |
| | 2/ 708.3.7.2 REPLACEMENT RECEPTACLES. FOR REPLACEMENT |
| | OF NONGROUNDING-TYPE RECEPTACLES WITH GROUNDING-TYPE |
| | RECEPTACLES AND FOR BRANCH CIRCUITS THAT DO NOT HAVE AN |
| | EQUIPMENT GROUNDING CONDUCTOR IN THE BRANCH CIRCUITRY, |
| | THE GROUNDING CONDUCTOR OF A GROUNDING-TYPE RECEPTACLE |
| | OUTLET SHALL BE PERMITTED TO BE GROUNDED TO ANY |
| | ACCESSIBLE POINT ON THE GROUNDING ELECTRODE SYSTEM, OR |
| | TO ANY ACCESSIBLE POINT ON THE GROUNDING ELECTRODE |
| | CONDUCTOR, IN ACCORDANCE WITH ARTICLE 250.130(C) OF |
| | CHAPTER 27 OF THE FLORIDA BUILDING CODE, BUILDING |
| | |
| | 1J) THE BEDROOM DOES INDICATE A SMOKE ALARM WITHIN THE |
| | UNIT OR ONE OUTSIDE OF THE BEDROOM. FBC RESIDENTIAL |
| | 313.2(2) AND NFPA 72. |
| | THE SMOKE ALARMS LOCATED WITHIN 20' OF COOKING WILL |
| | NEED TO BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE |
| | ALARMS AND SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20 |
| | FT) HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE |
| | EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE |
| | PHOTOELECTRIC TYPE. |
| | |
| | 2) 908.4 NUMBER OF ELECTRICAL OUTLETS. WHERE THE |
| | OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN |
| | EXISTING BUILDING IS CHANGED, THE NUMBER OF ELECTRICAL |
| | OUTLETS SHALL COMPLY WITH CHAPTER 27 OF THE FLORIDA |
| | BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY. |
| | 2008 NEC 210.50(A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FEET FROM A RECEPTACLE OUTLET. |
| | |
| | 2008 NEC 210.50(A)(2)(1) ANY SPACE 2 FEET OR MORE IN |
| | WIDTH (INCLUDING SPACE MEASURED AROUND CORNERS) AND |
| | UNBROKEN ALONG THE FLOOR LINE BY DOORS, FIREPLACES, AND |
| | SIMILAR OPENINGS. |
| | 2A) THE BEDROOM WALL COMMON WITH THE LIVING ROOM. |
| | |
| | 2B) THE LIVING ROOM WALL LEFT OF THE ENTRY DOOR. |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |