| Plan Review Notes For Permit 10090070 |
| Permit Number |
10090070 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-28 12:00:06 | MECHANICAL PLANS DENIED | | | 1) SEPARATE PERMIT AND PLANS REQUIRED FOR GREASE HOOD . | | | 2) PLEASE REFER TO SECTION 506.3.12.3 TERMINATION | | | LOCATION 2007 FBC. (M) | | | 3) PLEASE PROVIDE A DETAIL FOR THE EXHAUST AND SUPPLY | | | FAN CURBS TIE DOWN TO THE ROOF ,FROM THE ENGINEER. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|