| Plan Review Notes For Permit 10090070 |
| Permit Number |
10090070 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-27 10:42:09 | 4310 BROADWAY AVENUE | | | PERMIT NUMBER 10090070 | | | "BUILD-NEW ADA SERVICE COUNTER" | | | | | | | | | 1. ON SHEET A-1 AN EXHAUST HOOD IS SHOWN BUT ON PAGE | | | M-1 A NEW GREASE HOOD IS SHOWN. SEPARATE PLANS AND | | | PERMITS REQUIRED FOR THE INSTALLATION OF A HOOD, DUCT, | | | AND FIRE SUPPRESSION SYSTEM. THE HOOD EXTINGUISHING | | | SYSTEM SHALL MEET THE REQUIREMENTS OF THE UL 300 | | | STANDARD. | | | | | | 2. ON SHEET M-1 A REVISION FOR A RAISED PARAPET IS | | | SHOWN. THIS WORK DOES NOT CORRESPOND TO INFORMATION | | | LISTED ON THE PERMIT APPLICATION. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | | | | | | | |
|