Plan Review Notes
Plan Review Notes For Permit 10090025
Permit Number 10090025
Review Stop B
Sequence Number 2
Notes
Date Text
2010-10-07 11:52:38BUILDING PROVISO:
 THE CURRENT PLAN INDICATES AN EXIT LIGHT IN FRONT OF
 THE STORAGE ROOM PLEASE COMPLY WITH,
 FBC-B 1014.2.2 2EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL OR PARTIAL HEIGHT FIXED WALLS
 OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE REQUIRED
 WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA TO THE
 EXIT WITHOUT OBSTRUCTIONS.
  