2010-09-21 10:35:041732 W 45TH STREET
 PERMIT NUMBER 10090025
 "TENANT BUILD-OUT FOR SHOE STORE; REMOVE EXISTING
 WALLS-NEW GRID CEILING-ENLARGE EXISTING BATHROOMS"
  
  
 1. ON PAGE C-1, THE LOCATION MAP APPEARS TO BE
 INCORRECT. THE BUILDING IS WEST OF AUSTRALIAN AVENUE,
 NOT EAST OF AUSTRALIAN AVENUE.
  
 2. PLEASE VERIFY CORRECT ADDRESS FOR THE BUILDING.
 STAFF HAS CHECKED THE PROPERTY CONTROL NUMBER ON THE
 PERMIT APPLICATION AND IT COMES BACK TO 1700 45TH
 STREET NOT 1732 45TH STREET.
  
 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 4. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS
 OFTEN AS NECESSARY.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 6. HOW WILL EXIT ACCESS BE MAINTAINED IN THE STORE
 ROOM. PLEASE ADVISE HOW TRAVEL PATH WILL BE MAINTAINED.
  
 7. EXISTING FIRE WALLS ARE TO BE VERIFIED THAT THE ONE
 HOUR FIRE SEPARATION EXISTS AND THAT ALL PENETRATIONS
 ARE PROPERLY SEALED WITH APPROVED MATERIALS AS
 DESCRIBED ON PAGE A-3.
  
 8. PLANS DO NOT CALL OUT OR MAKE REFERENCE TO AUTOMATIC
 FIRE SPRINKLERS OR FIRE ALARM EQUIPMENT. THERE IS A
 NOTE ON PAGE E-2 "PROVIDE KNOX BOX FOR FIRE DEPT.
 W/SIGN STATING "FIRE ALARM CONTROL PANEL INSIDE" AT
 ENTRY TO LEADING TO FACP". COULD NOT LOCATE ANY FIRE
 ALARM CONTROL PANEL ON DRAWINGS.
  
 9. PLEASE PROVIDE MORE DETAILS ON THE PORTABLE FIRE
 EXTINGUISHERS DISPLAYED ON THE PLANS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION