| Notes |
| Date |
Text |
| 2010-09-07 16:01:08 | DENIED BY BUILDING | | | | | | 1) THE DESIGN PRESSURES ON THE PRODUCT APPROVAL (+37.0, | | | -40.0) ARE TOO LOW FOR A TWO STORY STRUCTURE LOCATED IN | | | EXPOSURE C OF A 140 MPH WIND ZONE. IN ACCORDANCE WITH | | | 2007 FBC TABLES R301.2(4) AND R301.2(3), IF THE MEAN | | | ROOF HEIGHT OF THE STRUCTURE IS 25 FEET THE REQUIRED | | | PRESSURES ARE +40.1 AND -44.7. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|