| Plan Review Notes For Permit 10080852 |
| Permit Number |
10080852 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-29 13:31:41 | RESIDENTIAL (R3) RENOVATION/ALTERATION PLUMBING REVIEW | | | CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PROVIDE PLUMBING RISER DIAGRAM WITH COMPLETE | | | INFORMATION AS REQUIRED BY SEC. 106.3.5.4 OF CITY | | | AMENDMENTS TO FBC. PLUMBING RISER DIAGRAM SUBMITTED ON | | | SHEET P1 IS MISSING THE PLUMBING FIXTURES DRAINAGE PIPE | | | SIZES AND LOCATION OF CLEANOUTS AS REQUIRED BY SEC. | | | P3005 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|