| Plan Review Notes For Permit 10080850 |
| Permit Number |
10080850 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-10 14:07:10 | 205 NORTH DIXIE HIGHWAY | | | PERMIT NUMBER 10080850 | | | PROVIDE FENCE AREA FOR RECORDS STORAGE | | | | | | | | | 1. WHAT IS THE PROPOSED HEIGHT OF THE STORAGE UNITS? | | | | | | 2. ARE THE SHELVING UNITS SOLID, SLATTED, OR OPEN. WILL | | | OVERHEAD FIRE SPRINKLER SYSTEM WATER BE ABLE TO WET | | | COMMODITIES ON THE LOWER LEVELS. | | | | | | 3. CARD READERS SHALL NOT INTERFERE WITH ANY EXITING. | | | | | | 4. PLEASE CLARIFY NOTE ON SHEET A-4 "PROVIDE OPENINGS | | | IN FABRIC AS REQUIRED FOR PENETRATION OF EXISTING FIRE | | | SPRINKLER PIPING". | | | | | | 5. PLEASE PROVIDE PROPOSED CLEARANCES FROM STORAGE TO | | | LIGHT FIXTURES, FIRE SPRINKLER HEADS, OR FLOOR CEILING | | | ASSEMBLIES. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|