Plan Review Notes
Plan Review Notes For Permit 10080787
Permit Number 10080787
Review Stop B
Sequence Number 3
Notes
Date Text
2010-12-20 17:01:53****PROVISO****
 ***PROVIDE AT INSPECTION***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FROM FIRST CORRECTION LIST: EITHER PROVIDE A WINDOW
 SCHEDULE OR REVISE THE FLOOR PLAN TO SHOW THE WINDOW
 SIZES, FBC1609.
  
 DOCUMENT SUBMITTED SHOWS WINDOW SIZE FOR OPENINGS 4, 1,
 AND 2. EITHER REVISE THE FLOOR PLAN OR PROVIDE A WINDOW
 SCHEDULE TO SHOW WINDOW SIZES FOR OPENINGS 3, 5, 6, 7.
  
 PER CONTRACTOR, ALL WINDOWS ARE SMALLER THAN MAX SIZE
 ALLOWED PER PRODUCT APPROVAL. REVISED FLOOR PLAN TO BE
 PROVIDED AT INSPECTION.
  
 2. ENGINEERING SHOW A MULLION, LOCATION UNCLEAR BASED
 ON DOCUMENTS PROVIDED. INCLUDE IN THE WINDOW SCHEDULE
 (OR REVISED FLOOR PLAN).
  
 PER CONTRACTOR, LOCATION WILL BE INDICATED ON FLOOR
 PLAN AND PROVIDED AT INSPECTION.
  
 3. ENGINEER IS TO REVISE ENGINEERING TO INCLUDE THE
 FOLLOWING INFORMATION:
 LOCATION SPECIFIC TO THE UNIT REGARDING PROPOSED
 INSSTALLATION
 THIRD PAGE OF ENGINEERING REFERS TO ADJUSTMENT FACTOR
 FOR 15' HEIGHT, REVISE OR PROVIDE EXPLANATION (ISN'T
 THIS A 4 STORY BUILDING?)
  
 PER ENGINEER, DISREGARD 3RD PAGE (NOTES FOR FILE ONLY,
 NOT INTENDED FOR PLAN REVIEW. DESIGN PRESSURES WERE
 CALCULATED CORRECTLY USING CORRECT BUILDING HEIGHT.
  