| 2010-12-20 17:01:53 | ****PROVISO**** |
| | ***PROVIDE AT INSPECTION*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. FROM FIRST CORRECTION LIST: EITHER PROVIDE A WINDOW |
| | SCHEDULE OR REVISE THE FLOOR PLAN TO SHOW THE WINDOW |
| | SIZES, FBC1609. |
| | |
| | DOCUMENT SUBMITTED SHOWS WINDOW SIZE FOR OPENINGS 4, 1, |
| | AND 2. EITHER REVISE THE FLOOR PLAN OR PROVIDE A WINDOW |
| | SCHEDULE TO SHOW WINDOW SIZES FOR OPENINGS 3, 5, 6, 7. |
| | |
| | PER CONTRACTOR, ALL WINDOWS ARE SMALLER THAN MAX SIZE |
| | ALLOWED PER PRODUCT APPROVAL. REVISED FLOOR PLAN TO BE |
| | PROVIDED AT INSPECTION. |
| | |
| | 2. ENGINEERING SHOW A MULLION, LOCATION UNCLEAR BASED |
| | ON DOCUMENTS PROVIDED. INCLUDE IN THE WINDOW SCHEDULE |
| | (OR REVISED FLOOR PLAN). |
| | |
| | PER CONTRACTOR, LOCATION WILL BE INDICATED ON FLOOR |
| | PLAN AND PROVIDED AT INSPECTION. |
| | |
| | 3. ENGINEER IS TO REVISE ENGINEERING TO INCLUDE THE |
| | FOLLOWING INFORMATION: |
| | LOCATION SPECIFIC TO THE UNIT REGARDING PROPOSED |
| | INSSTALLATION |
| | THIRD PAGE OF ENGINEERING REFERS TO ADJUSTMENT FACTOR |
| | FOR 15' HEIGHT, REVISE OR PROVIDE EXPLANATION (ISN'T |
| | THIS A 4 STORY BUILDING?) |
| | |
| | PER ENGINEER, DISREGARD 3RD PAGE (NOTES FOR FILE ONLY, |
| | NOT INTENDED FOR PLAN REVIEW. DESIGN PRESSURES WERE |
| | CALCULATED CORRECTLY USING CORRECT BUILDING HEIGHT. |
| | |