Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-09-07 13:56:15*****APPROVED WITH COMMENTS*****
  
 1) ADD THE FLORIDA FIRE PREVENTION CODE (FFPC) 2007
 EDITION TO THE CODE LIST.
  
 2) PROVIDE DOOR CLOSERS ON FIRE RATED DOORS PER SECTION
 8.3.3.3 OF FFPC NFPA 101, 2006 EDITION.
  
 3) NEW FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING WITH THE WORDING, "FIRE
 BARRIER - PROTECT ALL OPENINGS." SUCH LETTERING SHALL
 BE 4-INCHES TALL, HALF-INCH WIDE, AND NOT MORE THAN 15
 FEET ON CENTER PER SECTION 8.3.2.4 OF FFPC NFPA 101,
 2006 EDITION.
  
 4) SEVERAL "PLAN NOTES" ARE NOT RELEVANT TO THIS
 PROJECT (STAIRS, GARAGES, EGRESS WINDOWS ETC.).
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW