| Notes |
| Date |
Text |
| 2010-09-07 13:56:15 | *****APPROVED WITH COMMENTS***** | | | | | | 1) ADD THE FLORIDA FIRE PREVENTION CODE (FFPC) 2007 | | | EDITION TO THE CODE LIST. | | | | | | 2) PROVIDE DOOR CLOSERS ON FIRE RATED DOORS PER SECTION | | | 8.3.3.3 OF FFPC NFPA 101, 2006 EDITION. | | | | | | 3) NEW FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED | | | WITH SIGNS OR STENCILING WITH THE WORDING, "FIRE | | | BARRIER - PROTECT ALL OPENINGS." SUCH LETTERING SHALL | | | BE 4-INCHES TALL, HALF-INCH WIDE, AND NOT MORE THAN 15 | | | FEET ON CENTER PER SECTION 8.3.2.4 OF FFPC NFPA 101, | | | 2006 EDITION. | | | | | | 4) SEVERAL "PLAN NOTES" ARE NOT RELEVANT TO THIS | | | PROJECT (STAIRS, GARAGES, EGRESS WINDOWS ETC.). | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | WPB FIRE PLAN REVIEW | | | 561-805-6730 |
|