2010-09-07 18:41:39BUILDING PLAN REVIEW
 PERMIT: 10080783
 ADD: 5700 GEORGIA AVE
 CONT: ADVANCED AIR & PLUMBING
 TEL: (561)722-1846
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
 1) 2HOUR FIRE RATED WALL REQUIRES A 1 1/2 HR OPENING
 PROTECTIVES PER FBC-B TABLE 715.4 AND 715.4.7 DOOR
 CLOSING. FIRE DOORS SHALL BE SELF- OR AUTOMATIC CLOSING
 IN ACCORDANCE WITH THIS SECTION.
  
 2)FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."