2010-08-31 08:58:23BUILDING REVIEW FOURTH CHECKLIST.
  
 1- ROOF OVER USING GAF MATERIALS CAN'T BE DONE ON THIS
 BUILDING. THERE ARE TWO NOTICE OF ACCEPTANCES FOR GAF
 RECOVERY DECKS. THEY ARE NOA 08-0221.08 AND 08-0221.11.
 NONE OF THE APPROVED ASSEMBLIES LISTED ON THESE NOA'S
 CAN'T BE USED IN THIS BUILDING BECAUSE THEY ARE LIMITED
 BY GENERAL LIMITATION #9. THIS LIMITATION DOESN'T ALLOW
 NAIL ENHANCING TO INCREASE THE DESIGN PRESSURES OF THE
 ASSEMBLY. SEE GENERAL LIMITATION #9 ON LAST PAGE OF
 NOA'S. THE DESIGN PRESSURES LISTED ON THE APPROVED
 ASSEMBLIES ARE TOO LOW TO MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE.
 THEREFORE, PROPOSED INSTALLATION IS NOT ALLOWED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712