| Plan Review Notes For Permit 10080761 |
| Permit Number |
10080761 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-12-06 15:00:46 | 222 LAKEVIEW AVENUE, SUITE 1400 | | | MASTER PERMIT NUMBER 10080761 | | | REVISION TRACKING NUMBER 10110436 | | | "REVISED CEILING LAYOUT INCLUDING LIGHTING AND AC | | | DIFFUSERS" | | | | | | | | | 1. CARD READERS ARE DISPLAYED IN BOTH STAIRWELLS. CARD | | | READERS ARE NOT ALLOWED TO BE INSTALLED IN STAIRWELLS. | | | PLEASE SEE NFPA 101 THE LIFE SAFETY CODE SECTION | | | 7.1.3.2.1 (6) OF WHAT EQUIPMENT IS ALLOWED TO BE | | | CONTAINED WITHIN AN EXIT ENCLOSURE. IN ADDITION NFPA | | | 101 THE LIFE SAFETY CODE 7.2.1.5.7.1 SPEAKS TO STAIR | | | ENCLOSURE DOORS. ALSO 7.2.1.5.7 DISCUSSES STAIR | | | ENCLOSURES. | | | | | | 2. IF CARD READERS ARE INSTALLED AT THE ELEVATOR | | | LOBBIES HOW DOES A TRANSIENT VISITOR TO THE SPACE EXIT | | | THIS AREA WITHOUT AN ACCESS CARD. ACCESS TO BOTH EXITS | | | ARE MADE INACCESSIBLE AND WHEN THE FIRE ALARM SYSTEM | | | ACTIVATES IS IT THE ENTIRE BUILDING OR THE FLOOR OF | | | INCIDENT, FLOOR ABOVE AND FLOOR BELOW. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | | | | | | | | | | |
|