Plan Review Notes
Plan Review Notes For Permit 10080761
Permit Number 10080761
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2010-12-06 15:00:46222 LAKEVIEW AVENUE, SUITE 1400
 MASTER PERMIT NUMBER 10080761
 REVISION TRACKING NUMBER 10110436
 "REVISED CEILING LAYOUT INCLUDING LIGHTING AND AC
 DIFFUSERS"
  
  
 1. CARD READERS ARE DISPLAYED IN BOTH STAIRWELLS. CARD
 READERS ARE NOT ALLOWED TO BE INSTALLED IN STAIRWELLS.
 PLEASE SEE NFPA 101 THE LIFE SAFETY CODE SECTION
 7.1.3.2.1 (6) OF WHAT EQUIPMENT IS ALLOWED TO BE
 CONTAINED WITHIN AN EXIT ENCLOSURE. IN ADDITION NFPA
 101 THE LIFE SAFETY CODE 7.2.1.5.7.1 SPEAKS TO STAIR
 ENCLOSURE DOORS. ALSO 7.2.1.5.7 DISCUSSES STAIR
 ENCLOSURES.
  
 2. IF CARD READERS ARE INSTALLED AT THE ELEVATOR
 LOBBIES HOW DOES A TRANSIENT VISITOR TO THE SPACE EXIT
 THIS AREA WITHOUT AN ACCESS CARD. ACCESS TO BOTH EXITS
 ARE MADE INACCESSIBLE AND WHEN THE FIRE ALARM SYSTEM
 ACTIVATES IS IT THE ENTIRE BUILDING OR THE FLOOR OF
 INCIDENT, FLOOR ABOVE AND FLOOR BELOW.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  
  
  