| Plan Review Notes For Permit 10080761 |
| Permit Number |
10080761 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-10 13:21:23 | 222 LAKEVIEW AVENUE, SUITE 1400 | | | PERMIT NUMBER 10080761 | | | | | | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | | SYSTEM REMODELING. | | | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER SYSTEM REMODELING. | | | | | | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. | | | | | | 4. NEW FIRE DAMPERS ARE TO BE DROP TESTED TO ENSURE | | | PROPER FUNCTION. | | | | | | 5. INSTALLATIONS OF SOFFITS SHALL NOT INTERFERE WITH | | | ANY OPERATION OF ANY FIRE SPRINKLER HEADS. | | | | | | | | | APPROVED PROVISO | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|