2010-08-24 15:38:06RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- SELECTED APPROVED ASSEMBLY FROM PAGE 37 OF NOA
 SUBMITTED IS LIMITED BY GENERAL LIMITATION #9 WITH
 DESIGN PRESSURES OF -45PSF. GENERAL LIMITATION #9
 DOESN'T ALLOW NAIL ENHANCING. NEED NAIL ENHANCING TO
 COMPLY WITH THE DESIGN PRESSURES OF SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE. SELECT ANOTHER ASSEMBLY WITH
 GENERAL LIMITATION #7 AND PROVIDE THE REQUIRED RAS 117
 CALCULATIONS.
  
 2- NOA 06-0410.06 SUBMITTED REQUIRES SIGNED AND SEALED
 RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION
 #7. PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS.
  
 3- ACCORDING TO THE MIAMI-DADE WEBSITE THE FILE FOR NOA
 06-0410.06 SUBMITTED IS CLOSED. NEED TO PROVIDE CURRENT
 NOA.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER