| Plan Review Notes For Permit 10080699 |
| Permit Number |
10080699 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-24 15:38:06 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- SELECTED APPROVED ASSEMBLY FROM PAGE 37 OF NOA | | | SUBMITTED IS LIMITED BY GENERAL LIMITATION #9 WITH | | | DESIGN PRESSURES OF -45PSF. GENERAL LIMITATION #9 | | | DOESN'T ALLOW NAIL ENHANCING. NEED NAIL ENHANCING TO | | | COMPLY WITH THE DESIGN PRESSURES OF SEC. R301 OF 2007 | | | FLORIDA RESIDENTIAL CODE. SELECT ANOTHER ASSEMBLY WITH | | | GENERAL LIMITATION #7 AND PROVIDE THE REQUIRED RAS 117 | | | CALCULATIONS. | | | | | | 2- NOA 06-0410.06 SUBMITTED REQUIRES SIGNED AND SEALED | | | RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION | | | #7. PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS. | | | | | | 3- ACCORDING TO THE MIAMI-DADE WEBSITE THE FILE FOR NOA | | | 06-0410.06 SUBMITTED IS CLOSED. NEED TO PROVIDE CURRENT | | | NOA. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|