| Plan Review Notes For Permit 10080689 |
| Permit Number |
10080689 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-25 15:57:47 | RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- ENGINEER TO REVISE WIND DESIGN CRITERIA AND | | | PRESSURES. ACCORDING TO THE 2009 REVISIONS SEC. | | | 1609.4.3 THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT | | | "B". REVISE AS REQUIRED. | | | | | | 2- ANY ROOFING EQUIPMENT REMOVAL REQUIRES SEPARATE | | | PERMIT. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|