2010-08-25 09:26:17RISER DIAGRAM SHOWS #3 WIRE TO ATM NEED TO SHOW SIZE OF
 BRANCH CIRCUIT PROTECTION AND WHAT SIZE
 WIRE TO SECOND ATM
  
 ALSO NEED TO SUBMIT PANEL SCHEDULE AND SHOW SIZE OF
 WIRE FROM METER TO ATM PANEL AND WHAT SIZE MAIN IN
 PANEL.
  
 SUBMIT FAULT CURRENT CALC AIC RATING OF MAINS AND BC
 BREAKERS.
  