| 2011-02-02 15:14:43 | ADD: 2510 BROADWAY |
| | CONT: JHAMTREE |
| | TEL: (561)602-0009 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 2ND REVIEW |
| | |
| | 1A) COMPLIED. |
| | |
| | 1B) SEMI- COMPLIED. SHEET SP-1 INDICATES AN OCCUPANT |
| | LOAD OF 52 OCCUPANTS, PLEASE REVIEW SECTION / TABLE |
| | 1015.1 WHICH WILL REQUIRE (2) POINTS OF EGRESS, AND |
| | THEY WILL TO MEET THE REQUIREMENT FOR 1/2 THE DIAGONAL |
| | DISTANCE APART FBC-B 1015.2.1. |
| | |
| | 1C) THE PROPOSED DOOR# (02) IS LOCATED2.5 FEET FROM |
| | THTE PROPERTY LINE SEE SP-1, PLEASE REVIEW FBC-B TABLE |
| | 704.7 FOR ALLOWABLE OPENINGS, UNPROTECTED OR PROTECTED, |
| | 0-5 FEET OPENINGS ARE NOT ALLOWED. |
| | |
| | 2-6) COMPLIED. |
| | |
| | 7) EVEN IF THE DESIGNEER OF RECORD PULL THE DOOR# 02 |
| | BACK BEYOND THE 0-3' ALLOWING FOR PROTECTED OPENINGS |
| | THE OTHER ISSUE WILL BE WITH THE EXIT DISCHARGE MEETING |
| | THESE REQUIREMENTS: |
| | |
| | 2007/ 2009 FBC-B 1024.3 EXIT DISCHARGE LOCATION. |
| | EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE |
| | LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT |
| | LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS |
| | THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE |
| | PROTECTED IN ACCORDANCE WITH SECTION 704 BASED ON FIRE |
| | SEPARATION DISTANCE. |
| | |
| | 2007/ 2009 FBC-B 1024.4 EXIT DISCHARGE COMPONENTS. EXIT |
| | DISCHARGE COMPONENTS SHALL BE SUFFICIENTLY OPEN TO THE |
| | EXTERIOR SO AS TO MINIMIZE THE ACCUMULATION OF SMOKE |
| | AND TOXIC GASES. |
| | |
| | 2007/ 2009 FBC-B 1024.5 EGRESS COURTS. EGRESS COURTS |
| | SERVING AS A PORTION OF THE EXIT DISCHARGE IN THE MEANS |
| | OF EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF |
| | SECTION 1024. |
| | |
| | 2007/ 2009 FBC-B 1024.5.1 WIDTH. THE WIDTH OF EGRESS |
| | COURTS SHALL BE DETERMINED AS SPECIFIED IN SECTION |
| | 1005.1, BUT SUCH WIDTH SHALL NOT BE LESS THAN 44 |
| | INCHES. |
| | |
| | THE CONTRACTOR SUBMITTED A PRODUCT APPROVAL FOR DOOR # |
| | 2 QUALITY ENGINEERED PRODUCT CO. INC. FOR WIND AND |
| | LARGE MISSILE IMPACT BUT NO TESTING REPORT FOR THE FIRE |
| | RATING OF DOOR, 2007/ 2009 FBC-B TABLE 715.4. |
| | |
| | 8) THE COVER SHEET INDICATES THE PREVIOUS TENANT TO BE |
| | A AUTO REPAIR GARAGE MAKING THIS A S-1 OCCUPANCY. A |
| | CHANGE IN OCCUPANCY REQUIRES IMPACT FEE REVIEW. BEFORE |
| | A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST |
| | BE PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF |
| | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| | CALL (561)233-5025 FOR MORE INFORMATION. |
| | |