| Plan Review Notes For Permit 10080639 |
| Permit Number |
10080639 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-14 18:21:47 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. SCOPE OF WORK ON PERMIT APPLICATION INDICATES "A/C | | | UNIT ON ROOF." NO INFORMATION WAS PROVIDED REGARDING | | | ANY NEW A/C EQUIPMENT ON PLANS. PROVIDE EQUIPMENT | | | SCHEDULE WITH INSTALLATION DETAILS PER FBC-B 106.1.1 | | | AND 106.3.5. | | | | | | 2. PLANS APPEAR TO SHOW UNCONDITIONED SPACE BEING | | | CONVERTED TO CONDITIONED SPACE. THIS CONSTITUTES AN | | | ADDITION PER DEFINITIONS IN FBC-B 13-202. SHOW | | | COMPLIANCE WITH ENERGY CODE REQUIREMENTS FOR AN | | | ADDITION PER FBC-B 13-101.1.2, INCLUDING SUBMISSION OF | | | AN ENERGY CODE COMPLIANCE FORM AND APPENDED COOLING | | | LOAD CALCULATIONS. | | | | | | 3. PROVIDE VENTILATION CALCULATIONS FOR THE NEW | | | OCCUPANCY OF THE CONVERTED SPACE IN ACCORDANCE WITH | | | FBC-EB 909.1. | | | | | | 4. PROVIDE DUCT LAYOUT SHOWING THE AIR DISTRIBUTION | | | SYSTEM FOR THE NEWLY CONVERTED SPACE PER FBC-M 603.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|