| Plan Review Notes For Permit 10080639 |
| Permit Number |
10080639 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-17 11:23:28 | 2510 BROADWAY | | | PERMIT NUMBER 10080639 | | | | | | 1. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 2. BUILDING ADDRESS NOT SHOWN ON ELEVATION DRAWINGS. | | | THE BUILDING ADDRESS SHALL BE A MINIMUM OF AT LEAST 6" | | | HIGH AND AT LEAST 1" WIDE AND IT SHALL CONTRAST WITH | | | THE BACKGROUND THAT IT IS AFFIXED TO. | | | | | | 3. SINCE NO COOKING EQUIPMENT IS SHOWN, NO COOKING IS | | | ALLOWED. ANY COOKING THAT PRODUCES SMOKE OR GREASE | | | LADEN VAPORS SHALL BE PROTECTED BY A HOOD,DUCT, AND | | | FIRE SUPPRESSION SYSTEM. SEPARATE PLANS AND PERMITS | | | REQUIRED. | | | | | | 4. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND | | | CEILINGS SHALL BE CLASS A OR B AND NOT C AS LISTED ON | | | THE PLANS. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|