| 2010-09-14 13:58:04 | BUILDING PLAN REVIEW |
| | PERMIT: 10080639 |
| | ADD: 2510 BROADWAY |
| | CONT: T B D |
| | TEL: (561)853-7013 EDMUND THOMPSON |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1A) PLEASE INDICATE ON SHEET A-1THE COMMON PATH OF |
| | TRAVEL WITH ALL KIOSK AND STANDS THAT WILL BE LOCATED |
| | IN THE MERCANTILE OCCUPANCY, THE COMON PATH OF TRAVEL |
| | CAN NOT EXCEED 75'-0 FOR A SINGLE EXIT MERCANTILE |
| | OCCUPANCY. FBC-B 1014.3, |
| | |
| | 1B) SHEET SP-1 INDICATES AN OCCUPANT LOAD OF 52 |
| | OCCUPANTS, PLEASE REVIEW SECTION / TABLE 1015.1 WHICH |
| | WILL REQUIRE (2) POINTS OF EGRESS, AND THEY WILL TO |
| | MEET THE REQUIREMENT FOR 1/2 THE DIAGONAL DISTANCE |
| | APART FBC-B 1015.2.1. |
| | |
| | 1C) THE PROPOSED DOOR# (02) IS LOCATED2.5 FEET FROM |
| | THTE PROPERTY LINE SEE SP-1, PLEASE REVIEW FBC-B TABLE |
| | 704.7 FOR ALLOWABLE OPENINGS, UNPROTECTED 0-5 FEET |
| | OPENINGS ARE NOT ALLOWED. |
| | |
| | 2) BOTH LS-1 & A-1 THE PLANS INDICATE A NEW HANDICAPPED |
| | RAMP BUT NO BOTTOM LANDING IS INDICATED PLEASE PROVIDE |
| | COMPLIANCE WITH : 11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| | ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM |
| | OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & |
| | LEVEL CLEARENCE. |
| | |
| | 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 3A) STOREFRONT WINDOWS |
| | 3B) STOREFRONT DOOR |
| | 3C) SHUTTERS IF GLAZED OPENINGS ARE NOT LARGE MISSILE |
| | IMPACT TESTED |
| | |
| | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5 BOTH SHEETS A-3 & A-5 INDICATE CUT WALL SECTIONS AND |
| | DETAILS FOR WALL RE-INFORCEMENT, THERE ARE NO DETAILS |
| | PROVIDING HOW COMPLIANCE WITH MAIN WIND FORCE RESISTING |
| | SYSTEM. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | FBC-B 2107.2 ACI 530. THE PLANS ARE MISSING THE LATERAL |
| | REINFORCEMENT OF EVERY OTHER COARSE. |
| | |
| | 6) PLEASE REVIEW SHEET A-4: |
| | 6A) DETAIL "C" THE GRAB BAR TO BE A MAXIMUM OF 12" FROM |
| | THE CORNER 11-4.16.4 TOILET ROOMS. |
| | |
| | 6B) DETAIL "B" THE WATERCLOSET IS TO BE LOCATED 18" |
| | CENTER LINE TO ADJACENT WALL. 11-4.16.2 FIGURE 11-28. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |
| | |
| | |